Accessing Boiler Parameters 
 
Control Parameter Default Settings. 
 

All Units are preset for correct operation.  
However if alterations are required to enhance the operation of the unit following the application of optional 
control the procedure is detailed below. 
 
The following Pages detail the parameters of the LMU64 controllers, For your assistance the Standard Factory 
settings are indicated. 
(Please note, the installer/commissioning engineer may have changed some of these settings to suit the system 
installed.) 
 
To access the parameters detailed below the boiler’s control panel must be used. (Only boilers supplied prior to 
2003 will require a QAA73 Room Unit to access the control parameters. The unit must be connected to the RU 
terminals or directly to the LMU64 controller via the X10:01 terminal.) 
 
There are three levels of access available, as follows.  If you cannot access a particular parameter line, please 
consult with MHG Heating Ltd Technical Department for further assistance. 

 

Level One  
(User) 

Press and release one of the 

 or  

 Program Buttons.  

The display will now indicate 

Use the Program Buttons to access the desired parameter line. Use the 

 

Button to alter the displayed parameter to the required setting.  
To save the adjusted parameter move to the adjacent parameter or press and 
release the INFO Button if you wish to exit this level. 
To exit without saving any adjustment press and release the MODE Button. 
 

Level Two  
(Installer) 

Press & Hold the  

 

Program Buttons simultaneously for at least 3 seconds.  

The display will indicate H90  
Use the Program Buttons to access the desired parameter line.  

Use the 

 

Button to alter the displayed parameter to the required 

setting. 
To save the adjusted parameter move to the adjacent parameter or press and 
release the INFO Button if you wish to exit this level. 
To exit without saving any adjustment press and release the MODE Button. 
 
 

Level Three 
(OEM) 

Press & Hold the 

Program Buttons simultaneously for at least 9 seconds.  

The display will indicate - - - - -   
A password is required to access this level.

 (Please contact MHG prior to accessing this as parameter level) 

Use the 

Program Buttons to access the desired parameter line. Use the 

 

Button to alter the displayed parameter to the required setting. 

To save the adjusted parameter move to the adjacent parameter or press and 
release the INFO Button if you wish to exit this level. 
To exit without saving any adjustment press and release the MODE Button. 
 

 
 
 
  
 

 

Содержание ProCon Boiler Controller

Страница 1: ...quired will be dependent upon the age of the appliance and the required system control All appliance operational mode adjustments and settings are undertaken via the unit control fascia Legend Button...

Страница 2: ...m settings Fault Indication Boiler Flow Temperature Stored HWS Operation Mode Outside Air Temperature Legend Button Label Function 1 WATER PRESSURE INDICATOR Not used In ProCon Ranges 2 MAIN DISPLAY F...

Страница 3: ...on that is available To access these parameters the following sequence must be undertaken Press and release the INFO Press Hold the Program Buttons simultaneously for at least 3 second The display wil...

Страница 4: ...ode will be generated and displayed by the failing appliance and all LPB networked RVA and Opentherm units If a fault is encountered by a RVA controller or is communicated to a RVA controller via the...

Страница 5: ...perating at correct speed LMU Version D E 130 Flue Temperature Too High Auto Resetting E 131 Fault With Burner E 132 External Safety Interlock Activated Open Circuit E 133 No Flame Detected After Fina...

Страница 6: ...Signal Lost During Operation 99 Flame Signal Lost During Operation 100 Flame Signal Lost During Operation 101 Flame Signal Not Detected Following Last Ignition Attempt 102 Flame Signal Not Detected F...

Страница 7: ...or Program Buttons The display will now indicate Use the Program Buttons to access the desired parameter line Use the Button to alter the displayed parameter to the required setting To save the adjus...

Страница 8: ...ch 1 Third Off 00 00 24 00 Time Switch 2 Heating Zone 2 Set Points AGU2 500 Clip and QAD36 sensors required P20 Heating Circuit 2 Time Switch 2 Day Selection 1 2 1 5 1 7 1 7 P21 Heating Circuit 2 Time...

Страница 9: ...er winter changeover temperature 30 C S W changeover deactivated 8 30 C 18 18 18 18 H532 Heating curve slope heating circuit 1 1 40 32 32 32 32 H533 Heating curve slope heating circuit 2 1 40 1 1 1 1...

Страница 10: ...units 3 12 0 16 1 1 1 2 3 12 H606 LPB segment number of LMU 0 14 0 0 0 0 H614 Program input LMU basis 0 255 3 3 3 3 H615 Function programmable output K2 LMU 0 255 0 0 0 0 H618 Progr input on clip in...

Страница 11: ...umber of Occurrences H713 5th Historical Fault Operating Phase H714 5th Historical Fault Operating Error Code H715 Current Historical Fault Number of Occurrences H716 Current Historical Fault Operatin...

Отзывы: