Start
01.01-31.12
--.--
dd:mm
663
End
01.01-31.12
--.--
dd:mm
668
Operating Level
Frost, Reduced
Frost Protection
Heating Circuit 1
700
Operating Mode HC1
Protection, Automatic, Reduced,
Comfort
Automatic
710
Comfort Setpoint
P712-P716
20.0
°C
712
Reduced Setpoint
P714-P710
16.0
°C
714
Frost Protection Setpoint
4-P712
10.0
°C
716
Comfort Setpoint Max
P710 - 35
35.0
°C
720
Heating Curve Slope
0.10 - 4.00
1.50
3.20
-
721
Heating Curve Displacement
-4.5 - 4.5
0.0
°C
726
Heating Curve Adaption
Off - On
Off
-
730
Summer/Winter heating limit
---/8
– 30
18
°C
732
24-Hour heating limit
---/-10
– 10
-3
°C
733
Ext’n 24-Hour heating limit
Yes
– No
Yes
740
Flow temp setpoint min
8
– P741
8
°C
741
Flow temp setpoint max
P740
– 95
85
°C
742
Flow temp setpoint room stat
---/P740 - ---/P741
---
°C
744
Swi-on ratio room stat
---/1
– 99
---
%
746
Delay Heat request
0
– 600
0
S
750
Room Influence
---/1
– 100
---
%
760
Room temp limitation
---/0.5
– 4
1
°C
761
Heating limit room controller
---/0
– 100
---
%
770
Boost heating
---/0
– 20
5
°C
780
Quick setback
Off, Down to Reduced Setpoint,
Down to Frost Protection Setpoint
To Reduced Setpoint
-
790
Optimum start control max
0 - 360
0
Min.
791
Optimum stop control max
0
– 360
0
Min.
794
Heat up gradient
0
– 600
60
Min/k
800
Reduced setp. increase start
---/P801
– 10
---
°C
801
Reduced setp. increase end
-30
– P800
-15
°C
809
Continuous pump operation
No
– Yes
No
812
Frost protection flow temp.
Off
– On
On
-
820
Overtempprot. pump circuit
Off
– On
On
-
830
Mixing valve boost
0
– 50
5
°C
832
Actuator type
Two Position
– Three Position
Three-position
-
833
Switching differential 2-pos
0
– 20
2
°C
834
Actuator running time
30
– 873
120
S
835
Mixing valve Xp
1
– 100
32
°C
836
Mixing valve Tn
10
– 873
120
S
850
Floor curing Function
Off, Function heating, Curing heating,
Function + Curing heating, Curing +
functional heating, Manually
Off
-
851
Floor curing setp. manually
0
– 95
25
°C
855
Floor curing setp. current
0
– 95
°C
856
Floor curing day current
0
– 32
861
Excess heat draw
Off, Heating mode, Always
Always
870
With buffer
No, Yes
Yes
-
872
With prim contr./system pump
No, Yes
Yes