51033211EN/AC
- Page 9
1. Presentation
1.4 Options
Transformer for galvanic isolation or earthing arrangement change
Important
: to simplify installation, connect the
Pulsar EX
treme
Transformer
downsteam of the
UPS
s.
Visit our Web site:
www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm
Nominal power
Nominal current
Input voltage
Voltage drop
Frequency
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Natural ventilation
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 4U)
Weight (tower)
Weight (rack)
Pulsar EX
treme
Transformer
3 kVA
16 A
230V (+15%, -20%)
< 3%
50/60 Hz (+/-10%)
3.75 kV / 5 M ohms
From 0
°
to +40
°
C
95%
Pn-10% > 1000 m
IP20 ANAN
443 x 173 x 465 mm
177 x 483 x 462 mm
24 kg
28 kg
Battery extensions for UPS backup times of 66 minutes
Pulsar EX
treme
offers a standard
backup time of 9 minutes.
To increase backup time, it is possible
to connect
Pulsar EX
treme
EXB
modules to the
UPS
s.
Visit our Web site:
www.mgeups.com/
products/pdt230/smallups/extreme/
guide.htm
.
Battery extensions for Pulsar EX
treme
:
The
Pulsar EX
treme
EXB
modules are available in "tower" and in "rack" models.
The
Pulsar EX
treme
EXB
modules
come with their connection cables.
+
+
+
Pulsar
EX
treme
EXB
Pulsar
EX
treme
EXB
Pulsar
EX
treme
EXB
Pulsar
EX
treme
EXB
9 min
20 min
36 min
66 min