Pulsar EX with the "manual
bypass" module ("Install"
version)
c
ensure that the "automatic bypass"
module 21 is properly installed;
c
take the "manual bypass" module 31 ;
c
plug the rear connectors into connectors
4 and 6 of Pulsar EX (see figure 5);
c
tighten the module using the 2 screws 24 ;
c
plug the connecting cable 26 into the
connector 12 of Pulsar EX;
c
connect the loads having to be supplied
by Pulsar EX:
v
open the cover protecting the terminal
blocks, pass the cable in the left cable-
clamp and connect the 3 wires (phase,
neutral and ground) to the output terminal
block 29 (XB2).
c
connect Pulsar EX to the AC supply;
v
pass the cable in the right cable-clamp
and connect the 3 wires (phase, neutral and
ground) to the input terminal block 30
(XB1) and put back the protective cover;
c
do not connect the supply cable to the AC
outlet if the battery extension module option
has to be installed, else directly consult the
"operation" section.