Installation
2.0
Scope
Guides the user through tools and equipment required for unpacking and performing connections required for initial
installation. Included are the electrical specifications, environmental recommendations and connection details.
The following describes installation procedures and recommendations for the Galaxy 3000 10-30 kVA UPS including
receiving, handling, and storage procedures. Prerequisites prior to installation; installation procedures and start-up
procedures are also included.
2.1
Electrical Specifications
Environmental Recommendations
Recommended environment
20° to 25° C (68° to 77° F.); 50% relative humidity; computer room or other tempera-
ture- and humidity-controlled environment
Operating temperature
0° to 40° C (32° to 104° F.) except battery
Storage
-20° to 50° C (-4° to 122° F.)
Humidity
up to 90% non-condensing (operating)
Altitude
sea level to 3,000 meters without derating
Acoustic noise
78 dBA Acoustic noise at rated load as measured 5 feet from the front of the UPS
module
Table 2-1: Electrical Specifications for the Galaxy 3000.
*
NOTE: Interrupted Transfer to Bypass Source:
If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not more than 500 msec. in duration).
1.
Bypass voltage greater than +10%, -10% from the UPS rated output voltage.
2.
Bypass frequency greater than ±2 Hz from the UPS rated output frequency.
2 — 1
86-172010-00 C05
Installation
Output Power Rating (0.8 PF)
UPS Voltage (input / output)
208/208
220/220
480/208
480/480
600/208
208/208
220/220
480/208
480/480
600/208
Input / Output Requirements & Frequency
Input Phase Rotation
Input Power Factor
Max. Nominal Input Current (-15% Input Line at 100% Load)
31 A
31 A
14 A
14 A
11 A
46 A
46 A
21 A
21 A
17 A
Output Current
28 A
26 A
28 A
12 A
28 A
42 A
39 A
42 A
18 A
42 A
DC Voltage
Max. Battery Current at Nominal Battery Voltage (240 VDC at 100% Load)
39 ADC
41 ADC
39 ADC
41 ADC
39 ADC
59 ADC
61 ADC
59 ADC
61 ADC
59 ADC
Max. Battery Current at Battery End-Voltage (198 VDC at 100% Load)
48 ADC
49 ADC
48 ADC
49 ADC
48 ADC
71 ADC
74 ADC
71 ADC
74 ADC
71 ADC
Battery Disconnect Current
Max. System Heat Generation (BTU/hr)
4777
6824
5800
6824
5800
7165
10235
8871
10235
8871
SR1 Maintenance Bypass and Isolation Switch Rating
50 A
50 A
50 A
50 A
50 A
50 A
50 A
50 A
50 A
50 A
Input / Output Fuse Current
70A
70A
70A
70A
70A
70A
70A
70A
70A
70A
Input and Optional Bypass Contactor Current
40A
40A
40A
40A
40A
40A
40A
40A
40A
40A
Output Power Rating (0.8 PF)
UPS Voltage (input / output)
208/208
220/220
480/208
480/480
600/208
208/208
220/220
480/208
480/480
600/208
Input / Output Requirements & Frequency
Input Phase Rotation
Input Power Factor
Max. Nominal Input Current (-15% Input Line at 100% Load)
61 A
61 A
27 A
28 A
22 A
91 A
91 A
41 A
42 A
33 A
Output Current
56 A
53 A
56 A
24 A
56 A
83 A
79 A
83 A
36 A
83 A
DC Voltage
Max. Battery Current at Nominal Battery Voltage (240 VDC at 100% Load)
78 ADC
80 ADC
78 ADC
80 ADC
78 ADC
116 ADC
120 ADC
116 ADC
120 ADC
116 ADC
Max. Battery Current at Battery End-Voltage (198 VDC at 100% Load)
94 ADC
97 ADC
94 ADC
97 ADC
94 ADC
141 ADC
146 ADC
141 ADC
146 ADC
141 ADC
Battery Disconnect Current
Max. System Heat Generation (BTU/hr)
8871
12965
10918
12965
10918
13306
19447
16377
19447
16377
SR1 Maintenance Bypass and Isolation Switch Rating
100 A
100 A
100 A
100 A
100 A
100 A
100 A
100 A
100 A
100 A
Input / Output Fuse Current
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
Input and Optional Bypass Contactor Current
110A
110A
110A
110A
110A
110A
110A
110A
110A
110A
125 A
10 kVA
15 kVA
20 kVA
30 kVA
198 VDC End Voltage 240 VDC Nominal 277 VDC Max. Maintenance Voltage
Three Phase, Three Wire + N + G 60 Hz
63 A (7 min. back-up time) 70 A (>7 min. back-up time)
>.98
198 VDC End Voltage 240 VDC Nominal 277 VDC Max. Maintenance Voltage
A,B,C Clockwise
A,B,C Clockwise
>.98
Three Phase, Three Wire + N + G 60 Hz
Содержание Galaxy 3000
Страница 12: ... This page left blank intentionally Galaxy 3000 10 30kVA x 86 172010 00 C05 ...
Страница 42: ... This page left blank intentionally Galaxy 3000 10 30kVA 3 12 86 172010 00 C05 ...
Страница 44: ... This page left blank intentionally Product Name 4 2 86 172010 00 C05 ...
Страница 48: ... This page left blank intentionally Product Name W 4 86 172010 00 C05 ...
Страница 52: ...Galaxy 3000 10 30kVA G 4 86 172010 00 C05 This page left blank intentionally ...
Страница 56: ......
Страница 57: ......