Introduction
page 1 — 3
Installation Manual
1.4
Receiving for Single Modules and Shared Systems
Before accepting the shipment from the freight carrier, inspect the exterior surfaces of all shipping containers or
packaging used, and the equipment, for damage that may have occurred during transit. If the shipping containers
or equipment show evidence of damage, note the damage on the receiving document (bill of lading) prior to signing
for receipt of equipment.
The equipment should be unpacked immediately after receipt, and inspected again to determine if any internal
shipping damage (broken components, disconnected wiring, loose connections, etc.) has occurred. Verify that the
equipment nameplate(s) correspond with the equipment ordered.
Damage claims should be filed directly with the carrier. Replacements for damaged components should be ordered
through MGE Customer Support Services at
1-800-523-0142
.
1.4.1
Handling
Carefully follow the handling instructions attached to the shipping materials.
1.4.2
Storage
If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location that is
protected against rain, splashing water, chemical agents, etc. The equipment should be covered with a tarpaulin or
plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.
IMPORTANT:
Batteries should be stored no longer than three (3) months
at 25° C (77° F) or lower prior to recharging. Exceeding the
recommended ambient storage temperature will induce bat-
tery back-up time and may adversely affect battery life.
1.4.3 Prerequisites to Installation
An efficient EPS 7000 installation depends on careful planning and site preparation. Installation of UPS equipment
must be handled by skilled technicians and electricians familiar with the special requirements of high-energy
electrical equipment. The installation must comply with the requirements of the National Electrical Code (NEC,
ANSI/NFPA 70, latest issue) and with local codes and requirements as applicable.
Before installation, the following environmental, mechanical, and electrical prerequisites must be fulfilled.
Carefully review the installation drawings supplied with the system and follow their instructions.
1.4.4
Environmental Considerations
The EPS 7000 is intended for use in an environment where control of temperature and humidity is provided.
The EPS 7000 generates heat and exhaust air through the top portion of its enclosures. Heat loss and air flow data
is provided in the installation drawings.
Содержание EPS 7000
Страница 1: ...EPS 7000 Single Module and Shared Systems Installation Manual w w w m g e u p s c o m...
Страница 10: ...This page left blank intentionally EPS 7000 Single and Shared Systems page c iv...
Страница 36: ...This page left blank intentionally EPS 7000 Single and Shared Systems page 3 8 Installation...
Страница 44: ...This page left blank intentionally EPS 7000 Single and Shared Systems page g 6...
Страница 46: ......
Страница 47: ......
Страница 48: ...1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 w w w m g e u p s c o m...