Comet installation and user manual: E-6761200XT/FA
Merlin Gerin by MGE UPS SYSTEMS
10.1
options
extended battery cabinet
As standard equipment, Comet comes with a battery providing a backup time (at
full rated load and a power factor of 0.6) of 8 minutes for the 5 kVA Comet S11
and S31 and 10 minutes for the other Comet models. This time can be increased
by installing 1 or 2 additional battery cabinets.
If Comet was not factory-set for the additional cabinets, the new configuration
must be entered by a MGE UPS SYSTEMS after-sales support technician.
Battery cells for an overall operating range of 30 mn
(at rated output power with a power factor of 0.6):
Comet
Battery cell
rated output of device (kVA)
characterisitics
5
7,5
10
15
20
30
series 11
height (mm)
730
910
910
width (mm)
360
400
400
depth (mm)
420
550
550
weight (kg)
72
118
149
series 31
height (mm)
730
910
910
1085
1085
width (mm)
360
400
400
560
560
depth (mm)
420
550
550
680
680
weight (kg)
72
118
149
270
340
series 33
height (mm)
1085
1085
1385
1385
width (mm)
460
560
610
610
depth (mm)
680
680
780
780
weight (kg)
176
270
355
480
Comet
Battery cell
rated output of device (kVA)
characterisitics
5
7,5
10
15
20
30
series 11
height (mm)
730
910
910
width (mm)
360
400
400
depth (mm)
420
550
550
weight (kg)
115
215
276
series 31
height (mm)
730
910
910
1085
1085
width (mm)
360
400
400
2 x 560
2 x 560
depth (mm)
420
550
550
680
680
weight (kg)
115
215
276
2 x 270
2 x 340
series 33
height (mm)
1085
1085
1385
1385
width (mm)
460
2 x 560
2 x 610
2 x 610
depth (mm)
680
680
780
780
weight (kg)
281
2 x 270
2 x 355
2 x 480
Battery cells for an overall operating range of 50 mn
(at rated output power with a power factor of 0.6):