Remote Power Off communication port (9)
Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize Pulsar MX RT with the RPO port, it is necessary to use a two-position switch (Normally Open
or Closed contact). Once switch is energized/de-energized, the UPS shuts off the display and the output of the UPS.
◗
The output devices can be powered again through auto bypass when the two-position switch is released (open or closed).
◗
The output devices will remain powered < 1 sec. after RPO activation.
Push the start button to return to normal operation.
Note:
The internal batteries will remain connected to the power sub-module after RPO activation.
The cable is not included.
Installation of optional
communication card (66102)
2.6 Required Protective Devices and Cable Cross-Sections
Recommended upstream protection
Required cable cross-sections
◗
Terminal-block cable capacity: 6 mm
2
, solid or stranded wire (maximum AWG 10).
◗
Capacity for earthing conductor: 6 mm
2
, solid or stranded wire (maximum AWG 10).
2 poles circuit breaker
To UPS Normal AC source
L1
G L2 (N)
L1
L2 (N)
UPS Power Rating
Upstream Circuit
Breaker
5000 RT
D curve - 35A
Pulsar MX
Installation
2 — 6
86-87050-00 A01
RJ12
5 V DC to 27 V DC
+
_
RJ12
5 VDC to 27 VDC
+
_
Remote power off contact normally closed (9)
Remote power off contact normally open (9)
◗
Signal:
activation voltage: 5 V DC to 27 V DC,
current: 10 mA max.
Содержание 5000 RT
Страница 2: ......
Страница 4: ...Pulsar MX 86 87050 00 A01...
Страница 10: ...This page left blank intentionally Pulsar MX 4 86 87050 00 A01...
Страница 30: ...This page left blank intentionally Pulsar MX 4 4 86 87050 00 A01...
Страница 36: ...Pulsar MX 86 87050 00 A01...
Страница 40: ...Pulsar MX 86 87050 00 A01...
Страница 42: ...Notes Pulsar MX 86 87050 00 A01...
Страница 43: ......