The UPS goes to sleep mode at the end of the battery backup time, until complete shutdown, due to tripping of the
battery-protection function against deep discharge.

Return of AC input power:
IMPORTANT: If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart
function (activated by return of AC input power) has not been disabled (see section 3.4).

The buzzer sounds continuously.
Press button  

22

to turn the buzzer OFF.

The equipment is no longer supplied with power.

End of backup time

The low-battery warning threshold can be set by the user, with the 

UPS

Driver

software (see section 3.4).

LED  

17

flashes.

The buzzer beeps every three seconds.

There is very little remaining battery backup time.  Close all
applications because UPS automatic shutdown is imminent.

Threshold for the low-battery warning

The AC-power source is outside tolerances, LED  

17

is ON, the buzzer

beeps three times.

The equipment connected to the UPS is supplied by the battery.

Transfer to battery power

3.3  Operation on battery power (following an AC input power failure)

3. Operation

test

1

2

BYPASS

test

%

1

2

BYPASS

test

1

2

BYPASS

Содержание 2200 RT 2U

Страница 1: ...www mgeups com Pulsar EX 2200RT 3200RT EXB 2200 3200 RT Installation and User Manual MGE UPS SYSTEMS INC...

Страница 2: ...lsar EX RT Models that must be followed during installation operation and maintenance of the UPS and batteries The Pulsar EX RT Models that are covered in this manual are listed below Pulsar EX 2200RT...

Страница 3: ...at is easily accessible The UPS can be disconnected from the AC power source by removing the power cord Check that the indications on the rating plate correspond to your AC power system and to the act...

Страница 4: ...lustrations on the following pages the symbols below are used LED off LED on LED flashing Audio indication Action Visual indication Notes tips and information help CAUTION Hazard to personnel or equip...

Страница 5: ...tion to the RS232 or USB communication port optional 13 2 5 Installation of the communication card option 13 2 6 Connections 14 3 Operation 3 1 Start up 15 3 2 LED indicators 15 3 3 Operation on batte...

Страница 6: ...Page 6 3400753300 AE 4 Maintenance 4 1 Troubleshooting 20 4 2 Replacement of the battery modules 22 5 Environment 24 6 Appendices 6 1 Technical characteristics 25 6 2 Glossary 26 6 3 Index 27 Contents...

Страница 7: ...ons 1 Presentation www mgeups com P U L S A R 3 75 inches 2U 25 75 inches EX 2200RT 26 00 inches EX 3200RT 17 24 inches 19 Rack mount 100 80 50 20 test 1 2 BYPASS E X Model Part Weight Number Ibs kg P...

Страница 8: ...0R and EX 3200RT L5 30P L5 30R Connector for an additional battery module Connector for automatic detection of an additional battery module Pushbutton to test phase neutral inversion of AC power sourc...

Страница 9: ...et the End of battery life alarm 24 25 23 22 21 20 19 18 17 16 Status change in progress Supplied with power Operation on battery power Status of programmable outlet 2 Operation in ON LINE mode backup...

Страница 10: ...B communication cable Telescopic rails for mounting in 19 bay with mounting hardware CD ROM with the Solution Pac and UPS Driver software Product documentation Two supports for the upright position 2...

Страница 11: ...D for rack mounting of the UPS on the rails The rails and the necessary mounting hardware are supplied in the box along with the UPS see item 32 on page 10 2 Installation 2 2 Installation in rack pos...

Страница 12: ...ion using provided hardware in the package see item 32 on page 10 Pull out the MGE Logo and Model plates then rotate them as shown 2 Installation 2 3 Installation in tower position P U L S A R P U L S...

Страница 13: ...2 and USB communication ports cannot operate simultaneously 31 30 1 Connect the RS232 30 or USB 31 communication cable to the serial port or the USB port on the computer 2 Connect the other end of the...

Страница 14: ...re it is possible to program the interruption of power to the two programmable outlets 5 during operation on battery power thus reserv ing backup power for the priority loads The battery begins chargi...

Страница 15: ...Percent load drawn by the protected equipment when button 23 is pressed 3 Operating faults flashing LED and beeps 27 Overload 26 UPS fault 25 Battery fault or end of life warning 24 Site wiring Fault...

Страница 16: ...r OFF The equipment is no longer supplied with power End of backup time The low battery warning threshold can be set by the user with the UPS Driver software see section 3 4 LED 17 flashes The buzzer...

Страница 17: ...he RS232 30 cable is properly connected UPS Driver installation 1 Insert the Solution Pac CD ROM containing the UPS Driver software into your computers CD ROM drive 2 Open the file Manager and select...

Страница 18: ...sfer to bypass if overload Transfer to bypass following a fault whatever the conditions on the AC power source Options 100 V 127 V Converter 50 Hz F 1 to 10 in 1 steps 0 to 110 in 10 steps Enabled cli...

Страница 19: ...e and restart it as indicated previously 6 Activate the RPO external contact to test the function 7 To return to normal operation deactivate the RPO external contact and restart the UPS using button 1...

Страница 20: ...life buttons 22 and 23 long beep once simultaneously for 3 seconds per hour It is advised to replace both batteries at See the section on maintenance the same time with the same rating as the origina...

Страница 21: ...the distribution of devices on the outlets LED 26 flashes and UPS electronics have detected a UPS fault Restart the UPS the buzzer sounds Depending on the UPS personalization parameters continuously s...

Страница 22: ...front panel B Remove the 2 screws Removal of the battery modules CAUTION Load will not be protected during this procedure Batteries constitute a danger electrical shock burns The short circuit curren...

Страница 23: ...erse order e g G F E To maintain an identical level of performance and safety use battery modules identical to that previously mounted in the UPS Press the two parts of the battery connector tightly t...

Страница 24: ...ing UPS packing materials must be recycled in compliance with all applicable regulations WARNING This product contains lead acid batteries Lead is a dangerous substance for the environment if it is no...

Страница 25: ...T 2200 VA 1540 W 3400753300 AE Page 25 1 Input voltage correspond to 33 66 100 of the nominal power rating 2 Adjustable from 100 V to 127 V using UPS Driver software 3 Frequency converter mode may be...

Страница 26: ...conversion i e the AC power from the AC power source is rectified AC DC then converted back DC AC to AC power Equipment Devices or systems connected to the UPS output Forced shutdown Ten second inter...

Страница 27: ...21 UPS ON OFF via software 17 UPS shutdown 18 W Web site 2 Weight 7 A Automatic bypass 9 18 20 Automatic start 17 B Bargraph 9 15 Battery End of backup time 16 Fault 9 15 Low battery warning 17 Recycl...

Страница 28: ...523 0142 Internet www mgeups com T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R 3400753300 AE 1660 Scenic Avenue Costa Mesa CA 92626 USA Main Number 714 557 1636 MGE UPS SYSTEMS INC U P...

Отзывы: