mFi Mason-Lite MFPST43 Скачать руководство пользователя страница 12

11

Combustible Floor Installations

Combustible Floor Installations

8” Metal Base

  The Mason-Lite Metal Base ensures the minimum 8” (eight 

inch) clearance above combustible flooring is maintained.

  A layer of 1/2” minimum Concrete Board is required on 

the top and mid section below as shown in 

Figure 17

. The 

required sizes are shown in the table below.

1/2” Thick Cement Board Dimensions

Model

A1

A2

B1

B2

MFPST-43

53”

28”

48”

23”

Figure 17 MFPST43 Metal Base Assembly

26 ga. galv.

Hearth Ember 

Shields

Anchor Bracket All-Thread Rods are secured to the 

bottom flange

 

of the Metal Base with eight (8) flat washers and eight (8) Nuts.

Place fiber blanket 

underneath base

Four (4) All-Thread Rods 

are secured to the 

top 

flange

 of the Metal Base 

with eight (8) flat washers 

and eight (8) Nuts.

53”

28”

!

 

    

 IMPORTANT:

Remember to tighten up nuts below the floor after fireplace 

installation in order to take up any slack in the threads.

Hearth Ember Shield:

  Metal safety stripping is required between the front of the 

Fireplace Hearth and Hearth Extension (not supplied). A 26 

gauge galvanized 4” wide metal strip can be used. The length 

needs to extend 2 inches beyond each side of the fireplace 

opening. If two strips are used, make sure they overlap at 

least two inches in the middle. The strip is placed about 2” into 

the underside of the platform at the front of both openings on 

the fireplace.

Note: When using an on-site-constructed hearth extension, 

you may use a sand-cement grout between the hearth and 

extension instead.

What You Will Need

What You Will Need

  You  will  find  that the  MASON-LITE Fireplace  is  designed 

to be completely assembled on-site, consisting of interlocking 

precast parts. You will need a thin-set type mortar for bonding. 

The parts of the fireplace are made of Mason-Lite’s incredibly 

strong blend of specialty cement and a light weight aggregate.
IMPORTANT! When applying mortar, it is imperative that the 

concrete blocks be maintained moist (not soaking) so they 

don’t absorb the water out of the mortar and cause adhesion 

to fail. Frequently run a damp sponge to the parts before 

mortar is applied!
  The installation of an anchor plate/damper is required 

but not supplied. You may purchase it from any chimney 

manufacturer or MFI. Also, an optional combustion air inlet 

MFP4-AK can be obtained from MFI. 

  Refractory Firebrick Liners also need to be installed. These 

should be a minimum of 1-1/8” (one and one-eight inches) 

thick. The liner will be applied within the walls and hearth area 

of the firebox.

Materials needed for concrete slab 

(non- combustible) installation

• 

Eight (8) pieces 3/8” rebar x 36” long (included with unit)

• 

Eight (8) pieces of rebar x 12” long (included with unit)

• 

Epoxy for securing rebar in footing / foundation

• 

Three (3) - 90 lb. bags of ready mix concrete with 1/4” or 

smaller aggregate

• 

Mason-Lite Mortar (one 50 lb. bag)

Materials needed for combustible

wood floor installation:

• 

Eight (8) pieces 3/8” rebar x 36” long (included with unit)

• 

Eight (8) 12” long, 1/2-13 UNC All-Thread with (24) nuts 

and washers

• 

8 inch Metal Base.

• 

1” ceramic fiber blanket the size of the hearth base to go 

under the metal base.

• 

½” cement boards.

• 

Four or more fasteners to attach metal base to floor joists

• 

Mason-Lite Mortar (at least one 50 lb. bag)

• 

Three (3) - 90 lb. bags of ready mix concrete with 1/4” or 

smaller aggregate.

Tools needed for both above installations:

•  One 4’ level

•  Roto-hammer with ½” drill bit

 

(needed for concrete slab 

install only)

•  Drill motor with mixer blade (to mix Mason-Lite Mortar)

•  Two empty 5 gallon buckets (to mix Mason-Lite Mortar)

•  One wheelbarrow

 

and shovel to mix concrete.

•  Grout bag

•  Triangular masonry trowel

•  Rubber hammer

•  Sponge and water bucket to wipe down and moisten parts 

prior to applying mortar.

Содержание Mason-Lite MFPST43

Страница 1: ...is book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when n...

Страница 2: ...STIBLE SHEATHING ABOVE OPENING TOP 18 457 mm SHEATHING OR TRIM TO OPENING SIDES 8 203 mm MANTLE ABOVE OPENING 12 305 mm OPENING TO SIDE WALL 24 610 mm HEARTH EXTENSION BEYOND FRONT 20 508 mm HEARTH EX...

Страница 3: ...rts Diagrams MFPST43 Fireplace Parts Diagrams Combustible Floor System Parts Combustible Floor System Parts Fireplace Parts Diagram Fireplace Parts Diagram 10 11 9 5 6 4 7 8 12 2 1 14 3 13 17 18 19 Fi...

Страница 4: ...LL WITH OUTSIDE AIR KIT ACCESS 4 HOLE 1 3 SIDE WALL 7 4 LOWER SIDE DOME 2 5 LINTEL 2 6 LOWER DOME FRONT 2 7 53 X4 X 3 X 1 4 ANGLE IRON 2 8 SPILL SWITCH BAFFLE 2 9 UPPER SIDE DOME 2 10 UPPER DOME FRONT...

Страница 5: ...8 57 I D FRAMING 18 MIN 2 MIN 2 MIN 2 MIN 2 MIN Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE M...

Страница 6: ...te note that a combustible wood header must be no closer than 2 to the top of the dome top Figure 5 Combustible Floor 28 57 I D FRAMING 2 MIN 2 MIN 20 MIN 2 MIN 12 MIN Not provided as part of fireplac...

Страница 7: ...nce manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular re...

Страница 8: ...ements Choice of materials and craftsmanship in fireplace and hearth finishing Note that each of these topics will be covered in detail and that the installer is expected to understand each phase comp...

Страница 9: ...himney System 2 This Mason Lite fireplace is intended as a supplemental heat source only It is not intended as a primary heat source 3 It is the responsibility of the contractor installer not the manu...

Страница 10: ...he floor joists Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be acco...

Страница 11: ...bers having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection res...

Страница 12: ...ce are made of Mason Lite s incredibly strong blend of specialty cement and a light weight aggregate IMPORTANT When applying mortar it is imperative that the concrete blocks be maintained moist not so...

Страница 13: ...y threading mortar as you stack each section one onto the next Constantly check for squareness and levelness while building each MFPST43 Fireplace Assembly MFPST43 Fireplace Assembly Field Assembly Pr...

Страница 14: ...s have such holding power you should look over the firebox assembly at the end and fill in any gaps especially joint connections with the mortar Needless to say you must make adjustments to be sure th...

Страница 15: ...tallations at each floor penetration above that where the Support Box is located as shown in Figure 29 Figure 29 Firestop Spacer with Living Space Above Ceiling Firestop Spacer Existing C e i l i n g...

Страница 16: ...shed Height to Combustible Floor Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces they cannot take any liability or responsibility for they w...

Страница 17: ...r greater For Mantel clearances see Figure 9 Walls that Adjoin your fireplace cannot be installed closer than 2 ft two feet to any adjoining walls in the room where the fireplace is Caution in Regards...

Страница 18: ...consequences resulting in an accident or malfunction If instructions are not followed the warranty on the product will become null and void Note that the most important aspect of the installation is...

Страница 19: ...ed all elements of the fireplace and chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first li...

Страница 20: ...exible brush from the top of the section downward to the elbow Then clean from the firebox up to the offset return section Be sure that you have covered the floor of the fireplace and out to the heart...

Страница 21: ...slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM...

Страница 22: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 23: ...his warranty makes MFI or any affiliate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property ther...

Отзывы: