mFi Mason-Lite MFPST43 Скачать руководство пользователя страница 10

9

Supporting Floor Systems

Supporting Floor Systems

It is the ultimate responsibility of the installer to ensure that 

proper concrete slab supports are used.

WARNING

 to the licensed design professional and/or building 

contractor: It is your responsibility to be certain  that the 

Mason-Lite can be properly supported by the combustible 

floor system on which the fireplace will rest.

For fireplace support foundations installed on concrete refer 

to Appendix I and II (

pages 20 & 21 

) for specific instructions.

Rebar locations

  Lay-out the position of the fireplace and drill holes where 

the rebar will be located. Secure eight #3 rebar 4 inches into 

concrete foundation with ITW Epoxy or Simpson Epoxy.  

Follow manufacturer’s instructions for installation of rebar into 

slab.

Wood Floor

  Anchorage of fireplace to wood floor construction is required. 

Refer to 

Figure 10

 for anchorage locations. Four anchors are 

required to attach to the sub-flooring framing.

Crawl Space or Upper Floor:

  For installation of firebox over combustible crawl spaces or 

upper floors, anchorage of the firebox is required. Illustrations 

of examples of possible anchorage methods are shown in 

Figures 10 thru 13 depending upon the type of floor framing. 

Final method of anchorage to be determined by licensed 

design professional.

  For conventional framing where the floor joists are parallel 

with the sides of the firebox, the addition of floor joists to align 

with the anchor brackets allows the brackets to be directly 

connected to the floor joists.

  Note that additional floor joists may be required to support 

the weight of the firebox and chimney. Where the floor joists 

run  parallel  to  the  front  of  the  firebox,  anchorage  can  be 

accomplished in like manner as shown in Figure 12 using 

blocking between the floor joist.

 

  For floors supported by I-Joists, the method of anchorage 

is illustrated in Figures 10 and 11. Figure 12 illustrates the 

general arrangement of anchorage to floor framing.

  It is important to take into consideration that the load for 

the Mason-Lite Fireplace must be considered as additional 

dead load that will have to be supported by the floor framing. 

Additional floor joists or I-joists may be required as determined 

by the licensed design professional.

  The weights to be considered are noted in 

Table I

. It is the 

task and responsibility of the general contractor/installer to see 

that the proper reinforcement for weight loads are made by a 

licensed design professional prior to the fireplace installation.

  As stated above, it is desirable to place additional framing 

for alignment of anchor rods. Refer to 

Figure 14

 for anchor 

rod locations.

  Attach the firebox side wall anchors to steel support frame 

by inserting all-thread rods through holes on the bottom flange 

on the steel support frame as shown in 

Figure 14

. Secure with 

two Ø 2” o.d. x Ø 9/16” i.d. x 0.10” Washers and two 1/2-13 

UNC Nuts.

Figure 10

Floor Sheathing 

not shown for 

clarity

Metal Base 

Assembly

EXAMPLE ONLY

2X FLOOR JOIST

2X FLOOR JOIST

A35 Brackets 

(16 required)

I-JOISTS

Anchor 

Brackets

Figure 12

I-Joist 

Anchoring 

Bottom 

View

Example Only

I-Jo

ist

Simpson 

Strong-Tie 

A-35 or 

equivalent

Figure 11

I-Joist Anchoring 

Top View

Example Only

Содержание Mason-Lite MFPST43

Страница 1: ...is book is valuable In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when n...

Страница 2: ...STIBLE SHEATHING ABOVE OPENING TOP 18 457 mm SHEATHING OR TRIM TO OPENING SIDES 8 203 mm MANTLE ABOVE OPENING 12 305 mm OPENING TO SIDE WALL 24 610 mm HEARTH EXTENSION BEYOND FRONT 20 508 mm HEARTH EX...

Страница 3: ...rts Diagrams MFPST43 Fireplace Parts Diagrams Combustible Floor System Parts Combustible Floor System Parts Fireplace Parts Diagram Fireplace Parts Diagram 10 11 9 5 6 4 7 8 12 2 1 14 3 13 17 18 19 Fi...

Страница 4: ...LL WITH OUTSIDE AIR KIT ACCESS 4 HOLE 1 3 SIDE WALL 7 4 LOWER SIDE DOME 2 5 LINTEL 2 6 LOWER DOME FRONT 2 7 53 X4 X 3 X 1 4 ANGLE IRON 2 8 SPILL SWITCH BAFFLE 2 9 UPPER SIDE DOME 2 10 UPPER DOME FRONT...

Страница 5: ...8 57 I D FRAMING 18 MIN 2 MIN 2 MIN 2 MIN 2 MIN Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE M...

Страница 6: ...te note that a combustible wood header must be no closer than 2 to the top of the dome top Figure 5 Combustible Floor 28 57 I D FRAMING 2 MIN 2 MIN 20 MIN 2 MIN 12 MIN Not provided as part of fireplac...

Страница 7: ...nce manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular re...

Страница 8: ...ements Choice of materials and craftsmanship in fireplace and hearth finishing Note that each of these topics will be covered in detail and that the installer is expected to understand each phase comp...

Страница 9: ...himney System 2 This Mason Lite fireplace is intended as a supplemental heat source only It is not intended as a primary heat source 3 It is the responsibility of the contractor installer not the manu...

Страница 10: ...he floor joists Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be acco...

Страница 11: ...bers having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection res...

Страница 12: ...ce are made of Mason Lite s incredibly strong blend of specialty cement and a light weight aggregate IMPORTANT When applying mortar it is imperative that the concrete blocks be maintained moist not so...

Страница 13: ...y threading mortar as you stack each section one onto the next Constantly check for squareness and levelness while building each MFPST43 Fireplace Assembly MFPST43 Fireplace Assembly Field Assembly Pr...

Страница 14: ...s have such holding power you should look over the firebox assembly at the end and fill in any gaps especially joint connections with the mortar Needless to say you must make adjustments to be sure th...

Страница 15: ...tallations at each floor penetration above that where the Support Box is located as shown in Figure 29 Figure 29 Firestop Spacer with Living Space Above Ceiling Firestop Spacer Existing C e i l i n g...

Страница 16: ...shed Height to Combustible Floor Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces they cannot take any liability or responsibility for they w...

Страница 17: ...r greater For Mantel clearances see Figure 9 Walls that Adjoin your fireplace cannot be installed closer than 2 ft two feet to any adjoining walls in the room where the fireplace is Caution in Regards...

Страница 18: ...consequences resulting in an accident or malfunction If instructions are not followed the warranty on the product will become null and void Note that the most important aspect of the installation is...

Страница 19: ...ed all elements of the fireplace and chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first li...

Страница 20: ...exible brush from the top of the section downward to the elbow Then clean from the firebox up to the offset return section Be sure that you have covered the floor of the fireplace and out to the heart...

Страница 21: ...slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM...

Страница 22: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 23: ...his warranty makes MFI or any affiliate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property ther...

Отзывы: