CHAPTER 2: POWER REQUIREMENTS
12
■
Burst Current
— The maximum rms current during a
period of around one second. The Burst Current is used
as a rating for magnetic breakers. It is also used for cal-
culating the peak voltage drop in long AC cable runs
according to the following formula:
V pk (drop) = I pk x R (cable total)
The Burst Current can also be used to calculate the AC
looping capability of Acheron Designer.
■
Ultimate Short-Term Pea
k
Current
— A rating for fast-
reacting magnetic breakers.
■
Inrush Current
— The spike of initial current encoun-
tered when powering on.
You can use Table 2 as a guideline for selecting cable
gauges and circuit breaker ratings for the system’s operat-
ing voltage.
The minimum electrical service amperage required by an
Acheron Designer loudspeaker system is the sum of the
Maximum Long-Term Continuous Current for each loud-
speaker. An additional 30 percent above the minimum
amperage is recommended to prevent peak voltage drops at
the service entry.
NOTE:
For best performance, the AC cable
voltage drop should not exceed 10 V, or
10 percent at 115 V and 5 percent at 230 V. Make
sure that even with AC voltage drops that the AC
voltage always remains within the operating win-
dows.
ELECTRICAL SAFETY GUIDELINES
Pay close attention to these important electrical and safety
guidelines.
■
The Acheron Designer requires a grounded outlet.
Always use a grounded outlet and plug.
■
Do not use a ground-lifting adapter or cut the AC cable
ground pin.
■
Do not exceed the current capability of the 20-amp AC
Input connector for the loudspeaker. When looping loud-
speakers, consider the total current draw for all loud-
speakers on the circuit, including the first loudspeaker.
■
Make sure the AC power cable for the loudspeaker has
the appropriate power plug (on the other end) for the
area in which you will operate the loudspeaker. In addi-
tion, the AC power cable must be rated for the total cur-
rent draw of all loudspeakers looped from the power
source.
■
Do not operate the unit if its power cable is frayed or bro-
ken.
■
Keep all liquids away from the Acheron Designer to avoid
hazards from electrical shock.
Table 2: Acheron Designer Current Draw
Current Draw
115 V AC
230 V AC
100 V AC
Idle Current
0.23 A rms
0.19 A rms
0.24 A rms
Maximum Long-Term
Continuous Current
1.58 A rms
0.83 A rms
1.78 A rms
Burst Current
3.1 A rms
1.4 A rms
3.6 A rms
Ultimate Short-Term
Peak Current
12.0 A peak
8.0 A peak
12.4 A peak
Inrush Current
25 A peak
54 A peak
20 A peak
Earth ground
Chassis ground