-6- 

CT ratio 

Three kinds of transformation ratio indications :   
(1)convert  the  transformation  ratio  based  on  the 
adjustable  basic  value  of  5A  for  secondary  circuit 
current;  (2)convert  the  transformation  ratio  based  on 
10kV-YY  of  10kV/380V,  that  means  1st  means  the 
current  of  the  line  under  380V,  2nd  means  the 
secondary  circuit  current  of  CT  under  the  380V,  and 
then calculate the  ratio  between  the  10KV  line  and  the 
secondary circuit; 
(3)the  measured current  ratio can  be  calculated  by  the 
measured CT ratio between the primary and secondary 
circuit. 

Reference 

Range 

Reference range of transformation: 0.00A ~ 99.99A, the 
default secondary circuit    current is transformed to 5A; 

Range of Ratio 

error 

(F.Er) 

0.0% ~ 9.9%, the error between the measured CT ratio 
and the preset CT ratio   

Range of CT 

ratio 

0000

9999/0.0A

9.9A 

Range of Ratio 

error 

0.0%

  9.9%, the principal machine can sound a alarm 

of “beep - beep – beep” if the measured value is more 
than the preset error. 

Phase polarity 

Symbol 

  indicated for in-phase positive polarity 

Symbol 

  indicated for in-phase negative polarity 

Indication of 

Phase 

Sequence 

Cursor  in  clockwise  rotation  and 

“Positive  Phase”   

indicated for positive phase sequence 
Cursor  in  counterclockwise  rotation  and 

“Negative 

Phase”    indicated for negative phase sequence   

Indication of 

Error 

Symbol “Error” indicated if    the tester can’t identify the 
phases, polarity,    and phase sequence properly;   

Data Storage 

1500 sets of dada memory; press the Left arrow key to 
select  data,  and  to save  and  auto-number  the selected 
data  (the  good  condition  of  data  available  under 
power-down or battery replacement) 

Automatic   

Recording 

Interval Time 

From  00  minutes  to  99  minutes,  the  tester  stops 
automatic record if being set to 00 minutes; the principal 
machine  doesn’t  shut  down  automatically  if  being  set 
from 01 minutes to 99 minutes.   

Содержание MEWOI1500D

Страница 1: ...MEWOI1500D THREE CHANNEL WIRELESS HV CT RATIO TESTER WWW MEWOI COM...

Страница 2: ......

Страница 3: ...8 V OPERATIONS 9 1 POWER ON OFF OF HV DETECTOR 9 2 POWER ON OFF OF PRINCIPAL MACHINE 10 3 TEST OF HV CURRENT 11 4 TEST LV CURRENT 14 5 TEST OF CT RATIO POLARITY 16 6 DETECTION ON PHASE SEQUENCE 20 7 A...

Страница 4: ...12 DATA UPLOAD 22 VI SETTINGS 22 1 SET CT RATIO 23 2 SET ERROR 23 3 SET TIME 24 4 SET BACKLIGHT 24 VII BATTERY REPLACEMENT 24 VIII ACCESSORIES 25...

Страница 5: ...en using this tester in any cases especially in which the voltage circuit bears the voltage of AC100V or more The tester shall be applied connecting insulating rod with the hand holding on the fifth r...

Страница 6: ...hall be used to gently rub down the tester Stop using and mothball then leave it to authorized organization for handling in case that continuing use can cause safety hazard due to the performance of t...

Страница 7: ...munication link etc it adopts the wireless transmission signal that is capable of penetrating wall obstacles with a direct line transmission distance of about 30m MEWOI1500D tester is widely applicabl...

Страница 8: ...ity moisture proof strong shock resistance bending resistance high insulation high flexibility and so on Monitoring Software Functions such as real time monitoring historical data search accessing bro...

Страница 9: ...se sequence and leaker in the three channel high low voltage current transformer and the voltage transformers Power supply HV Detector DC6V alkaline batteries 1 5V AAA 4 Principal machine DC6V alkalin...

Страница 10: ...ange of Ratio error 0 0 9 9 the principal machine can sound a alarm of beep beep beep if the measured value is more than the preset error Phase polarity Symbol indicated for in phase positive polarity...

Страница 11: ...A displayed Zero signal indication The symbol is shown if the principal machine can t receive the signal from the HV detector Backlight Control Available ON OFF means to open close the backlight Alarm...

Страница 12: ...size Outer diameter 32mm inner diameter 24mm 1m piece 5 pieces Lead length of LV current clamp 2 m Piece Dielectric strength AC100kV rms between HV detector cover and the 5 th insulating rod the AC10...

Страница 13: ...rations Check if any damage exists for each part before operating the tester it can be put into use only after being qualified Install the battery according to the requirements set forth in the manual...

Страница 14: ...respectively and the data measured by LV current clamps of CT1 CT2 and CT3 can be displayed on the position of R S and T on screen respectively the LCD can display the symbol if the principal machine...

Страница 15: ...sualty Only when all of the five insulating bars are connected can the high voltage line be detected otherwise there may be the danger of electric shock resulting in personal injury or casualty Danger...

Страница 16: ...nd can be shown on R phase If the principal machine shows that the primary circuit current value is OL it is indicated that the primary circuit current exceeds the upper limit of the high voltage dete...

Страница 17: ...13 Notice please take the instrument away from the wire after the detection is finished for a safe operation It is available to measure HA current leaker by the tester...

Страница 18: ...e 600V or 10A otherwise there can be the danger of electric shock resulting in personal injury or casualty 1 Connect three LV current clamps to the corresponding principal machines power on the machin...

Страница 19: ...15 3 Reference Diagram Recording the circuit current monitoring leakers from equipment Detecting cable leakers in wall Detecting leaker from grounding wire...

Страница 20: ...ption of battery 5 Test of CT ratio polarity 1st the current detected by single channel HV detector the primary current for CT 2nd the current collected by three channel LV current clamp the secondary...

Страница 21: ...benchmark of secondary current in the range from 0 00A to 99 99A CT ratio of transformation based on benchmark of 10kV YY the HV detector collects the secondary current from the busbar 380V of transf...

Страница 22: ...row key from the CT ratio display mode to the error test mode For example The pretest current transformer is a low voltage terminal CT of 10kV 380V transformer which primary current is 151 5A and whic...

Страница 23: ...ratio display mode and press the MEM key and the Down arrow key to set the basic value for transformation of secondary current while calculate the CT ratio on basis of the new basic value The default...

Страница 24: ...25 more than the T phase otherwise it is negative The cursor rotates clockwise on LCD under the positive phase sequence and rotates counterclockwise under negative phase sequence as shown in the figu...

Страница 25: ...n is completed The tester can save up to 1 500 sets of data if the memory is full the symbol Full is shown it is necessary to clear the memory for the more storage 10 Data search Press the MEM key to...

Страница 26: ...and run the monitoring software if the software displays the serial port is open and connected it is available to access the historical data which can be uploaded to the computer and saved under the...

Страница 27: ...he error by the above preset its setting range is from 0000 to 9999 0 0 9 99A Press the Left or Right arrow key to move the cursor press the Up or Down arrow key continuously or interruptedly to chang...

Страница 28: ...or interruptedly to change the setting range move the cursor to the OK or Cancel position and press the MEM key to return the previous menu 4 Set backlight Press the Left or Right arrow key to move th...

Страница 29: ...ied batteries Paying special attention to the specification and electrode of new batteries close the battery cover tighten the two new screws 3 Press the POWER key to check if the instrument starts up...

Страница 30: ......

Страница 31: ......

Страница 32: ...Your Testing Specialist...

Отзывы: