2. Declaration of Conformity 

The  device  was  tested  according  to  the  applicable  standards.

Conformity was proofed. The declaration of conformity is available

at the manufacturer BTR NETCOM GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the

device.  In  case  of  questions  that  cannot  be  answered  with  these

instructions please consult supplier or manufacturer. 
The indicated installation directions or rules are applicable to the

Federal Republic of Germany. If the device is used in other countries

it  applies  to  the  equipment  installer  or  the  user  to  meet  the 

national directions. 

Safety Instructions

Keep the applicable directions for industrial safety and prevention

of accidents as well as the VDE rules. 
Technicians  and/or  installers  are  informed  that  they  have  to 

electrically  discharge  themselves  as  prescribed  before  installation

or maintenance of the devices.
Only qualified personnel shall do mounting and installation work

with the devices, see section “qualified personnel”. 
The information of these instructions have to be read and under-

stood by every person using this device. 

Symbols

Warning of dangerous electrical voltage 

Danger

means  that  non-observance  may  cause  risk  of  life, 

grievous bodily harm or heavy material damage. 

Qualified Personnel

Qualified personnel in the sense of these instructions are persons

who are well versed in the use and installation of such devices and

whose professional qualification meets the requirements of  their

work. 
This includes for example:

l

 Qualification  to  connect  the  device  according  to  the  VDE 

specifications and the local regulations and a qualification to put

this device into operation, to power it down or to activate it by

respecting the internal directions.

l

 Knowledge of safety rules.

l

 Knowledge about application and use of the device within the

equipment system etc. 

3. Technical Data

Modbus Interface

Protocoll                             Modbus RTU
Transmission rate                1200 ... 115200 Bd 

                                          (factory setting 19200 Bd Even)

Cabling                               RS485 two wire bus with voltage 

                                          equalizing cable in bus / line topology

Supply

Operating voltage range    20 ... 28 V AC/DC (SELV)
Current consumption         200 mA (AC) / 75 mA (DC)
Relative duty cycle              100 %

Input

Voltage input                      30 V AC/DC
High-signal recognition      >8 V AC/DC

Output

Output contacts                 2 changeover contacts
Switching voltage max.      250 V AC
Continuous current max.    16 A / relay (80 A / 20 ms)
Total current for 

all contacts                         25 A

Housing

Dimensions WxHxD            2.0 x 2.8 x 3.0 in. (50 x 70 x 75 mm)
Weight                                126 g
Mounting position              any
Mounting                           standard rail TH35 per IEC 60715
Mounting in series              the maximum quantity of modules 

without space                     connected in line is limited to 15 or to 

                                          a maximum power consumption of 

                                          2 Amps (AC or DC) per connection to 

                                          the power supply. For any similar block 

                                          of additional modules a separate 

                                          connection to the power supply is 

                                          mandatory.

Material

 Housing                            Polyamide 6.6 V0

 Terminal blocks                 Polyamide 6.6 V0

Cover plate                         Polycarbonate
Type of protection 

(IEC 60529)

 Housing                            IP40

 Terminal blocks                 IP20

Terminal blocks

Supply and bus

 4 pole terminal block        max. AWG 16 (1,5 mm²) solid wireg

                                          max. AWG 18 (1,0 mm²) stranded wire

Wire diameter                     min. 0.3 mm up to max. 1.4 mm

                                          (terminal block and jumper plug are 

                                          included to each packing unit)

Module connection

 Input/Output                     max. AWG 12 (4.0 mm²) solid wire

                                          max. AWG 14 (2.5 mm²) stranded wire

Wire diameter                     min. 0.3 mm up to max 2.7 mm

Temperature range

Operation                           -5 °C ... +55 °C
Storage                               -20 °C ... +70 °C
Protective circuitry              polarity reversal protection of 

                                          operating voltage

                                          polarity reversal protection of supply 

                                          and bus

Display

Operating and bus activity green LED
Error indication                   red LED
Status of the 

inputs & outputs                yellow LED

1. Description

The  Modbus  module  with  4  digital  inputs  and  2  relay  outputs  is

designed for local switching operations. It is suitable to receive for

example light switches and window contacts in a room and to ope-

rate two light bands or to be used as sunblind control. It can also

be  used  to  control  two  motor  driven  fire  dampers  or  for  many

other  applications.  We  recommend  to  protect  the  relay  contacts

additionally by a RC-element or high inductive loads. The relays are

provided with a manual control facility. Depending on the position

of the jumper (below the faceplate) the inputs can be operated as

contact and voltage inputs (A1, 24 V AC/DC; jumper J - A2) or with

actuation to GND (A2; jumper J - A1. Inputs and outputs can be

operated  and  scanned  via  a  Modbus-Master.  Addressing  of  the

module as well as baud rate and parity setting are done with the

two address switches (x1 / x10) on the front. Possible settings are

addresses 00 to 99 and baud rates 1200, 2400, 4800, 9600, 19200,

38400, 57600 und 115200 Bd.
The  device  does  not  participate  in  bus  communication  if  the

address is 00 (reserved for broadcast address).

89

92

90

Digital I/O Module

MR-DIO4/2

1108331326

5. Connection Diagram

4. Wiring Diagram

A1 = C1 = 24 V

A1 = C1 = 24 V

BTR NETCOM GmbH

Im Tal 2
78176 Blumberg
Germany

Phone +49 7702 533-0
Fax     +49 7702 533-189

Mounting instruction see
www.metz-connect.com

Содержание Logline MR-DIO4/2

Страница 1: ... DC High Signalerkennung 8 V AC DC Ausgangsseite Ausgangskontakte 2 Wechslerkontakte Schaltspannung max 250 V AC Dauerstrom max 16 A Relais 80 A 20 ms Summenstrom über alle Kontakte 25 A Gehäuse Abmessungen BxHxT 50 x 70 x 75 mm Gewicht 126 g Einbaulage beliebig Montage Tragschiene TH35 nach IEC 60715 Anreihbar ohne Abstand Nach dem Anreihen von 15 Modulen oder einer maximalen Stromaufnahme von 2 ...

Страница 2: ...GND 24V 24V GND GND ERROR ERROR B B A A MR DIO4 2 MR DIO4 2 B B A A BUSY BUSY x1 x1 x10 x10 MODBus RTU MODBus RTU A1 24 V A1 24 VA AC DC C DC N N L L Jumper unter Jumper unter der Blende der Blende Anschlussbeispiel 3 A2 GND A2 GND N N L L 1 1 4 4 C1 C1 C1 C1 12 12 22 22 2 2 3 3 C1 C1 C1 C1 1 11 1 21 21 14 14 24 24 1 1 2 2 3 3 4 4 24V 24V 24V 24V 24V 24V GND GND 24V 24V GND GND ERROR ERROR B B A A...

Страница 3: ...Modbus Kommando Parität und Bitrate haben die gleichen Werte wie bei der Einstellung über die Adressschalter Wenn Parity oder Baud 0 ist erfolgt keine Einstellung und Speicherung Der Registerinhalt wird im EEPROM gespeichert 06 0x06 Write Single Register Request Valid Register Address 0x41 65 Valid Register Value 2 Bytes Bit 15 8 Magic Number 0x53 83 zum Schutz vor versehent lichem Schreiben Nur m...

Страница 4: ...t for all contacts 25 A Housing Dimensions WxHxD 2 0 x 2 8 x 3 0 in 50 x 70 x 75 mm Weight 126 g Mounting position any Mounting standard rail TH35 per IEC 60715 Mounting in series the maximum quantity of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps AC or DC per connection to the power supply For any similar block of additional modules a separ...

Страница 5: ...ttings specified in the chart the factory setting applies Factory setting 19200 Bd Even 1 1 4 4 C1 C1 C1 C1 12 12 22 22 2 2 3 3 C1 C1 C1 C1 1 11 1 21 21 14 14 24 24 1 1 2 2 3 3 4 4 24V 24V 24V 24V 24V 24V GND GND 24V 24V GND GND ERROR ERROR B B A A MR DIO4 2 MR DIO4 2 B B A A BUSY BUSY x1 x1 x10 x10 MODBus RTU MODBus RTU J J 24V 24V GND GND Jumper below Jumper below the faceplate the faceplate Á Á...

Страница 6: ...as returned no response neither a normal response nor an exception response since its last restart clear counters operation or power up Continuation Software description 9 2 Bit rate setting with Modbus command Parity and bit rate have the same value as when setting them by address switch If Parity or Bit has the value 0 no setting or storage is carried out The register content is stored in the EE...

Отзывы: