Pinpoint the Fault
1
Keep the A-Frame parallel to the target cable.
2
Insert the A-Frame every 10-20 ft. Follow the arrow.
3
When the arrow changes direction, backtrack. Look at the number of bars
activated and compare them to number of bars you read at synchronization
point. If the number of bars is similar to the number of bars at
synchronization point, you have located the main fault.
4
Insert the A-Frame every two feet until the arrow changes direction again.
5
Move the A-Frame across the cable until a slight movement causes the
arrow to change direction. The fault is located at the center of the A-
Frame.
6
Check entire cable for multiple faults. If more faults are present, check the
active number at each fault site and compare it to the reference number.
The higher the active number the larger the fault.