DL7, DL7L
58
[7]: Enabling the option switches on the archiving of the alarm and control thresholds
exceeded alarm to the event file.
[8]: The recording of measurement results can be controlled by means of exceeded
alarm/control thresholds. Two different recording intervals can be set. The exceeded
threshold can switch from MAIN ARCHIVE interval I to MAIN ARCHIWE interval II.
14.3.4 Totalizers
Mode: Disabled
(Disabled, Unresettable, Resettable, Daily, Weekly, Monthly)
[1]
,
Unit: [None]
(text)
[2]
,
Multiplier: 1
(0.001, 1, 1000)
[3]
,
Resolution: 0
(0, 0.0, 0.00, 0.000, 0.0000)
[4]
,
Archiving: Disabled
(Disabled, Enabled)
[5]
[1]: Each totaliser may be set in one of the six positions. Disabled
– values are not
counted, Resettable
– user can zero the totaliser at any moment, Unresettable – user
cannot zero the totaliser, daily
– the totaliser is erased every 24 hours, Weekly - the
totaliser is erased after the elapse of a week, Monthly - the totaliser is erased after the
elapse of a month.
[2]: The unit is provided for reference purposes only. User can put in any unit which does
not affect the results displayed by the device.
[3]: The multiplier allows multiplication of the measurement results by one of the three
values selected from the list. For example, if a flow meter is connected to the device
measuring the flow in m
3
/s, and the user wants the result to be displayed in dm
3
/s the
multiplier should be set to 1000. In a converse situation, when the measurement would
be made in dm
3
/s, and the user would like the values counted by the totaliser to be
displayed in m
3
/s the value of the multiplier should be set to 0.001.
CAUTION!!
It has to be remembered that the multiplier value does not determine the
displayed unit and vice versa.
[4]: The number of decimal places displayed. It has no effect on the calculation accuracy
and can be changed any time without affecting the totalizer status.
[5]: Enables enabling or disabling the counter archiving. Selecting the screen is equivalent
to switching on the archiving.
!
All the settings of the individual channels may be copied and pasted to
another measurement channel. Detailed information is given in section
14.4 Communication settings
14.4.1 PORT ETHERNET
To ensure proper communication between the recorder and the master system, all
communication parameters need to be configured.
Main menu
Communication
Ethernet