DL7, DL7L
15
5.6 The input module measuring the temperature and voltage mV DL7-IN6TC
temperature measurements using thermometers (a complete list of sensors is given in
the chapter discussing the technical data),
compensation of the junction compensation - with a fixed value or a measurement using
another channel
linear measurement of the voltage within the range or sub-range -140 .. +140 mV,
6 measurement inputs galvanically separated from the remaining circuits.
each input has a separate pin type four-wire terminal block.
a two-colour LED diode informing about the module's operating status.
5.7 The voltage input module DL7-IN6V
interface with the standard output transducers and the voltage of 0-10V, 2-10V, 0-5V,
and 1-5V,
linear measurement of the voltage within the range or sub-range -10 .. +10 V,
6 measurement inputs galvanically separated from the remaining circuits.
each input has a separate pin type four-wire terminal block.
a two-colour LED diode informing about the module's operating status.
5.8 Universal input module DL7-IN3
interfacing with the active transducers with the standard current output 0/4-20mA (or
passive transducers with additional external power supply); temperature measurements
using the Pt, Ni, Cu, KTY type sensors (a complete list of sensors is given in the chapter
discussing the technical data); temperature measurements using thermocouples;
interface with the standard output transducers and the voltage of 0 .. 10V, -10 .. +10V;
linear current measurement within the range or sub-range of -20 .. +20 mA; linear
measurement of the resistance within the range or sub-range 0 .. 4000
Ω; linear
measurement of the voltage within the range or sub-range -140 .. +140 mV, -10 .. +10 V;
3 measurement inputs galvanically separated from the remaining circuits;
each input has a separate pin type eight-wire terminal block;
a two-colour LED diode informing about the module's operating status.
5.9 Binary inputs module DL7-IN6D
the ability to work in a toggle mode, frequency measurement mode or pulse counting,
the ability to track a binary signal open / close,
Frequency measurement in the range of 0.1 .. 1000 Hz (pulse counting 0.1 .. 100 Hz),
Cooperation with passive pulse transmitter (contact transistor configuration OC), the
source voltage or current pulses,
6 measurement inputs galvanically separated from the remaining circuits,
each input has a separate pin type three-wire terminal block,
a two-colour LED diode informing about the module's operating status.
5.10 Digital Input Module (Modbus RTU) DL7-IN2RS485 (24V)
designed to work with instruments and sensors that communicate with the RS-485 bus
according to the Modbus RTU protocol,
Possibility of reading and recording up to 25 digital values,