DL2
60
Register
tab
IO
[1]
Port: Disabled
(Disabled, 1, 2)
[2]
Device:
[device address]
[3]
Address:
[value]
[4]
Type: uint(16bit)
(uint (16bit), int (16bit), uint (32bit), uint (32bit) sw, int (32bit), int
(32bit) sw, float (32bit), float (32bit) sw, int (64bit), double (64bit))
[5]
[1]: Module
’s measurement channel number. Each of the modules provides 25
measuring channels, the numbering of which allows for easily assigning the
appropriate measurement to the display channel.
[2]:
The number of the module port used. Each module has two active ports.
[3]: Slave device address from which the data will be read.
[4]: Set the register's number from which data will be read. Available format: 3xxxx /
3xxxxx or 4xxxx / 4xxxxx, where: 3
input registers, 4
holding register and xxxx /
xxxxx
four / five digit address. To speed up the communication, set consecutive
register
’s numbers in increasing order. The value must be given in decimal system
MODBUS RTU / MODBUS TCP TRANSMISSION PROTOCOL
).
[5]: 10 formats of readings are available in the drop-down list, where: uint
– unsigned
integer, int
– signed integer, float – single precision floating point, double – double
precision floating point, sw
– swapped format (more information in section
). Choose a format that matches the specification of the sensor or device you
are reading.
OUT6RL
Mode: Disabled
(Disabled, Normally open, Normally closed, Pulsation)
[1]
[1]: In the
Normally open
mode the relay circuit is closed when an event is reported (e.g.
exceeded alarm-control threshold). In the
Normally closed
mode, the relay circuit is
normally closed when idle, and is opened when an event is reported.
Pulsation
-
when an event is reported, the relay circuit is closed and opened at approx. 1Hz
frequency
(e.g. a light indicator blinks - alarm notification). After the acknowledge, the
relay output remains active if the threshold is still exceeded (the indicator is lit). If the
exceeding returns to normal
– the relay output will be inactive.
OUT3
Mode: 0-20mA
(Disabled, 0-20mA, 4-20mA, 0-24mA, 0-5V, 0-10V)
[1]
Source: Channel 1
(Channel 1-30)
[2]
Failure value: Constant
(Disabled, Constant)
[3]
[1]: Setting the operating mode of a given output to generate standard loop current
signals: 0-20 mA, 4-20 mA, 0-24 mA or standard voltage signals: 0-5 V, 0-10 V,
(
Disabled
sets the output to 0-5 V mode and value 0 V).
[2]: Selection of the channel which value is to be retransmitted. The output span may be
set as a sub-range of retransmitted channel span by entering the process values for
minimum and maximum span value respectively.