Metrohm E1620 Скачать руководство пользователя страница 9

5.

OPERATING INSTRUCTIONS

5.1

Preliminary Checks

(1)

With the leads disconnected, select the 20m

 range

and switch on the instrument by pressing the test switch
and holding it depressed.

(2)

The low current warning lamp ‘I’ should light and the
LCD should indicate the overrange condition  as shown
in Fig. 1.

Fig. 1

(3)

If the warning lamp or the LCD display do not operate,
check that batteries have been correctly installed in the
instrument.

(4)

On releasing the test switch, the reading should remain
on the LCD for about two minutes after which the
instrument will automatically switch off. Where
customer test leads are used, their connection to the
item to be tested should be as illustrated in Fig. 4.

to 10.40m

 at 30ºC. Account should be taken of this effect in

making measurements.

When measuring the resistance of item, such as current shunts,
which have joints of dissimilar conductors, thermal EMFs can
affect the accuracy of the measurement. This condition can be
detected if the reading alters when the leads are reversed. To
compensate for this effect, the average of the two readings should
be taken as the true measurement.

5.7

Battery Replacement

If the ‘BAT’ symbol appears on the LCD during a test, testing
should  be  discontinued  until  the  batteries  are  replaced  or
recharged in the case of nickel–cadmium cells. Before accessing
the batteries, the test leads should be removed for safety reasons.
Access to the batteries is via the lid in the base of the instrument.
The two plastic screws should be loosened to allow the lid to be
removed.  The  discharged  batteries  can  then  be  removed  and
replaced with new or recharged batteries. The orientation of the
batteries should be as indicated by the polarity symbols in the
battery compartment. The lid can then be replaced and the plastic
screws tightened.

5.8

Fuse Replacement

Fuse  protection  is  provided  on  the  current  terminals,  C1  and
C2, and it is indicative of a blown fuse if the low current warning
lamp ‘I’ is lit and the resistance across terminals C1 and C2, is
less than 1

. The fuse is positioned in the battery terminal and

the same procedure, as was described in the previous section,
should be followed to access the fuse. The blown fuse should be

5.

OPERATING INSTRUCTIONS

5.1

Preliminary Checks

(1)

With the leads disconnected, select the 20m

 range

and switch on the instrument by pressing the test switch
and holding it depressed.

(2)

The low current warning lamp ‘I’ should light and the
LCD should indicate the overrange condition  as shown
in Fig. 1.

Fig. 1

(3)

If the warning lamp or the LCD display do not operate,
check that batteries have been correctly installed in the
instrument.

(4)

On releasing the test switch, the reading should remain
on the LCD for about two minutes after which the
instrument will automatically switch off. Where
customer test leads are used, their connection to the
item to be tested should be as illustrated in Fig. 4.

to 10.40m

 at 30ºC. Account should be taken of this effect in

making measurements.

When measuring the resistance of item, such as current shunts,
which have joints of dissimilar conductors, thermal EMFs can
affect the accuracy of the measurement. This condition can be
detected if the reading alters when the leads are reversed. To
compensate for this effect, the average of the two readings should
be taken as the true measurement.

5.7

Battery Replacement

If the ‘BAT’ symbol appears on the LCD during a test, testing
should  be  discontinued  until  the  batteries  are  replaced  or
recharged in the case of nickel–cadmium cells. Before accessing
the batteries, the test leads should be removed for safety reasons.
Access to the batteries is via the lid in the base of the instrument.
The two plastic screws should be loosened to allow the lid to be
removed.  The  discharged  batteries  can  then  be  removed  and
replaced with new or recharged batteries. The orientation of the
batteries should be as indicated by the polarity symbols in the
battery compartment. The lid can then be replaced and the plastic
screws tightened.

5.8

Fuse Replacement

Fuse  protection  is  provided  on  the  current  terminals,  C1  and
C2, and it is indicative of a blown fuse if the low current warning
lamp ‘I’ is lit and the resistance across terminals C1 and C2, is
less than 1

. The fuse is positioned in the battery terminal and

the same procedure, as was described in the previous section,

-7-

-7-

-14-

-14-

Содержание E1620

Страница 1: ...s WD24 4YY Tel 44 0 1923 441717 Fax 44 0 1923 446900 E mail sales martindale electric co uk Web www martindale electric co uk CMR0073 Issue 4 07 04 Martindale Electric Co Ltd Martindale Electric Co Lt...

Страница 2: ......

Страница 3: ...8 LIMITED WARRANTY PAGE 1 3 4 5 5 6 7 9 9 10 10 11 11 12 12 13 13 14 14 14 15 15 15 16 16 17 17 18 19 TABLE OF CONTENTS TABLE OF CONTENTS 1 SAFETY RULES 2 GENERAL DESCRIPTION 3 FRONT PANEL LAYOUT 4 P...

Страница 4: ...me or change specification price or design without notice and without incurring any obligation 14 LIMITED WARRANTY Martindale Electric Limited warrant instruments and test equipment manufactured by th...

Страница 5: ...anation Of Symbols Used Caution risk of electric shock Caution refer to the instruction manual 6 Do not touch exposed wiring connections or other live parts of an electrical circuit If in doubt check...

Страница 6: ...old Temperature IEC68 2 1 Dry Heat IEC68 2 2 Damp Heat IEC68 2 3 Drop Test IEC1010 Clause 8 4 Impact Test IEC1010 Clause 8 2 Weight 0 75kg with batteries and leads 6 3 Environmental Operating Temperat...

Страница 7: ...t of Kelvin leads and an instruction manual 3 FRONT PANEL LAYOUT The ranges are selected by a four position rotary switch and test is initiated by pressing the push button test switch While this switc...

Страница 8: ...on 2A and 20 ranges Test Current Accuracy 10 Max Circuit Resistance 1 2 on 20m range with 9V battery voltage 15 on 200m range removed and replaced with a fuse of the correct type and rating 5 9 Input...

Страница 9: ...and the same procedure as was described in the previous section should be followed to access the fuse The blown fuse should be 5 OPERATING INSTRUCTIONS 5 1 Preliminary Checks 1 With the leads disconne...

Страница 10: ...r copper As an example a copper conductor that has a resistance of 10 00m at 20 C will increase Current Leads 1 Shrouded 4mm safety plugs are required at one end of each lead as before 2 Insulated 16...

Страница 11: ...rior of the instrument requires cleaning it should be done with a sponge and a mild solution of Fig 3 9 If the BAT symbol appears on the LCD during these checks as shown in Fig 3 the batteries require...

Страница 12: ...unts PCB tracks switch and relay contacts etc v Checking compression joints on overhead lines accepted as there will be inaccuracies due to the resistance between the current terminals C1 and C2 being...

Отзывы: