Metrohm E1620 Скачать руководство пользователя страница 11

(vi)

Testing and maintenance of switchboard/ sub–
station equipment on such items as fuses,
joints, contacts and  bonds.

5.5

Customer Test Leads

The  Kelvin  crocodile  clips  supplied  with  the  instrument  are
suitable for connecting to conductors up to 15mm in diameter
or bus bars 15mm thick. There will be, however, instances where
the item being tested requires larger jaws, and the user is advised
to make up his own leads. Furthermore, there will be occasions
when longer leads are required due to the geometry of the item
being tested. The following guidance notes should assist in the
assembly of such leads:

Potential Leads

1.

Shrouded, 4mm, safety plugs are
required at one end of each lead for
connection to the E1620 measuring
sockets.

2.

Insulated, 16/0.2mm, tinned copper
wire is recommended.

3.

The two potential leads should be the
same length to minimise inaccuracies
due to unbalance.

4.

For practical reasons, the lead length
should be as short as possible to
                         minimise pick up.

Fig. 3

(9)

If the ‘BAT’ symbol appears on the LCD during these
checks, as shown in Fig. 3, the batteries require to be
replaced or recharged. Follow the instructions for
replacing batteries outlined in the proceeding section.

5.2

Precautions

(1)

Always ensure that the circuit to be measured is
switched off, isolated and completely de–energised
before connecting the test leads.

(2)

If it is probable that the instrument’s protection has been
impaired due to electrical, mechanical or environmental
damage, it must not be used. It should be returned to
the manufacturer or his appointed
agent for checking and repair.

(3)

To prevent damage to the liquid crystal display, the
minimum storage temperature of -20ºC must be
observed. It should also be noted that below 0ºC the
operation of this display will be sluggish.

(4)

If the exterior of the instrument requires cleaning, it
should be done with a sponge and a mild solution of

Fig. 3

(9)

If the ‘BAT’ symbol appears on the LCD during these
checks, as shown in Fig. 3, the batteries require to be
replaced or recharged. Follow the instructions for
replacing batteries outlined in the proceeding section.

5.2

Precautions

(1)

Always ensure that the circuit to be measured is
switched off, isolated and completely de–energised
before connecting the test leads.

(2)

If it is probable that the instrument’s protection has been
impaired due to electrical, mechanical or environmental
damage, it must not be used. It should be returned to
the manufacturer or his appointed
agent for checking and repair.

(3)

To prevent damage to the liquid crystal display, the
minimum storage temperature of -20ºC must be
observed. It should also be noted that below 0ºC the
operation of this display will be sluggish.

(4)

If the exterior of the instrument requires cleaning, it
should be done with a sponge and a mild solution of

(vi)

Testing and maintenance of switchboard/ sub–
station equipment on such items as fuses,
joints, contacts and  bonds.

5.5

Customer Test Leads

The  Kelvin  crocodile  clips  supplied  with  the  instrument  are
suitable for connecting to conductors up to 15mm in diameter
or bus bars 15mm thick. There will be, however, instances where
the item being tested requires larger jaws, and the user is advised
to make up his own leads. Furthermore, there will be occasions
when longer leads are required due to the geometry of the item
being tested. The following guidance notes should assist in the
assembly of such leads:

Potential Leads

1.

Shrouded, 4mm, safety plugs are
required at one end of each lead for
connection to the E1620 measuring
sockets.

2.

Insulated, 16/0.2mm, tinned copper
wire is recommended.

3.

The two potential leads should be the
same length to minimise inaccuracies
due to unbalance.

4.

For practical reasons, the lead length
should be as short as possible to
minimise pick up.

-9-

-9-

-12-

-12-

Содержание E1620

Страница 1: ...s WD24 4YY Tel 44 0 1923 441717 Fax 44 0 1923 446900 E mail sales martindale electric co uk Web www martindale electric co uk CMR0073 Issue 4 07 04 Martindale Electric Co Ltd Martindale Electric Co Lt...

Страница 2: ......

Страница 3: ...8 LIMITED WARRANTY PAGE 1 3 4 5 5 6 7 9 9 10 10 11 11 12 12 13 13 14 14 14 15 15 15 16 16 17 17 18 19 TABLE OF CONTENTS TABLE OF CONTENTS 1 SAFETY RULES 2 GENERAL DESCRIPTION 3 FRONT PANEL LAYOUT 4 P...

Страница 4: ...me or change specification price or design without notice and without incurring any obligation 14 LIMITED WARRANTY Martindale Electric Limited warrant instruments and test equipment manufactured by th...

Страница 5: ...anation Of Symbols Used Caution risk of electric shock Caution refer to the instruction manual 6 Do not touch exposed wiring connections or other live parts of an electrical circuit If in doubt check...

Страница 6: ...old Temperature IEC68 2 1 Dry Heat IEC68 2 2 Damp Heat IEC68 2 3 Drop Test IEC1010 Clause 8 4 Impact Test IEC1010 Clause 8 2 Weight 0 75kg with batteries and leads 6 3 Environmental Operating Temperat...

Страница 7: ...t of Kelvin leads and an instruction manual 3 FRONT PANEL LAYOUT The ranges are selected by a four position rotary switch and test is initiated by pressing the push button test switch While this switc...

Страница 8: ...on 2A and 20 ranges Test Current Accuracy 10 Max Circuit Resistance 1 2 on 20m range with 9V battery voltage 15 on 200m range removed and replaced with a fuse of the correct type and rating 5 9 Input...

Страница 9: ...and the same procedure as was described in the previous section should be followed to access the fuse The blown fuse should be 5 OPERATING INSTRUCTIONS 5 1 Preliminary Checks 1 With the leads disconne...

Страница 10: ...r copper As an example a copper conductor that has a resistance of 10 00m at 20 C will increase Current Leads 1 Shrouded 4mm safety plugs are required at one end of each lead as before 2 Insulated 16...

Страница 11: ...rior of the instrument requires cleaning it should be done with a sponge and a mild solution of Fig 3 9 If the BAT symbol appears on the LCD during these checks as shown in Fig 3 the batteries require...

Страница 12: ...unts PCB tracks switch and relay contacts etc v Checking compression joints on overhead lines accepted as there will be inaccuracies due to the resistance between the current terminals C1 and C2 being...

Отзывы: