1.2.7. Fan Curve
Figure 7 – External static pressure vs airflow at different fan speeds.
In order to assure an efficient operation, it is suggested to keep the external pressure
drops below 200 Pa.
Parameter
Unit
190L
260L
Airflow
Nominal air flow rate (variable range)
m
3
/h
450 (0-800)
Maximum fan power consumption
W
85
Max external static pressure
Pa
200 Pa
G - Air duct connections
mm
160
Minimum volume of room installation
m
3
30
Operating limits
Max air temperature
°C
40
Min air temperature
°C
-7
Max water temperature
°C
60
Max water pressure
MPa
0,6 or 1,0. Check nameplate