MTEK6000 SERIES USER'S MANUAL
3-12
January 2002
Calibrating the Differential Pressure
Transmitter (EFM Only)
NOTE
Pressing
esc
repeatedly from anywhere
within the calibration procedure will back
the operator out of calibration mode.
1.
Display the differential pressure by
pressing
F8
or jumping to 040302.
2.
Press
cal
. Enter your password at the
optional
PASSWORD?
prompt, if
required.
3.
The unit will enter calibration mode.
The display will alternate between
CALIBRATING
and the parameter label
(
Diff Press “H20 for
example
)
.
4.
Open both pressure connection valves.
5.
Open bypass valve and close both high
pressure and low-pressure transmitter
connection valves on manifold.
6.
Slowly open the high-pressure
transmitter connection valve and allow
the transmitter’s output to stabilize.
7.
Press
zero
. The display now shows:
ZERO> XX.XXX
NEW?>
XX.XXX represents the unit's default zero
value. If the current zero reference matches
the unit's default, simply press
ent
to collect
the new point. Otherwise, key in the value
of the current reference before pressing
ent
.
The unit should display Calculating
. . .
briefly, and then display the new point.
Pressing
esc
instead of
ent
at this point
aborts the operation and returns you to the
calibration prompt.
8.
Apply the span (full scale) reference to
the differential pressure sensor and wait
for the reading to stabilize
9.
Press
span
. The unit now shows:
SPAN> XX.XXX
NEW?>
As with the zero point, if the external
reference matches the default span value,
simply press
ent
. Otherwise, key in the
current value of the external reference, then
press
ent
. After pressing
ent
, the display
reading should immediately adjust to reflect
the new calibration point. Pressing
esc
instead of
ent
at this point aborts the
operation and returns the operator to the
calibration prompt.
10. Steps 5 - 9 are required only once. They
may be repeated as often as necessary
while in calibration, but only the most
recent point will be saved on completion
of calibration.
11. To permanently store the results of the
calibration press
ent
, and the unit will
prompt
Enter to accept Calibration
.
Simply press
ent
again to save the
calibration. Press
esc
to abort the
calibration.
12. Confirm that the bypass valve is open.
13. Slowly open the high-pressure valve.
14. Open the low-pressure valve.
15. Close the bypass valve.
Содержание MTEK6000 Series
Страница 6: ...MTEK6000 SERIES USER S MANUAL January 2002...
Страница 9: ...MTEK6000 SERIES USER S MANUAL January 2002 1 3 Figure 1 1 MTEK6000 exterior view...
Страница 10: ...MTEK6000 SERIES USER S MANUAL 1 4 January 2002 Figure 1 2 MTEK6000 interior view...
Страница 26: ...MTEK6000 SERIES USER S MANUAL 2 16 January 2002...
Страница 33: ...MTEK6000 SERIES USER S MANUAL January 2002 3 7 Figure 3 1 Optional Keypad and Display...
Страница 40: ...MTEK6000 SERIES USER S MANUAL 4 2 January 2002 Figure 4 1 Analog Output Option...
Страница 46: ...MTEK6000 SERIES USER S MANUAL 5 4 January 2002...
Страница 56: ...MTEK6000 SERIES USER S MANUAL A 10 January 2002...
Страница 58: ...MTEK6000 SERIES USER S MANUAL B 2 January 2000...
Страница 66: ...MTEK6000 SERIES USER S MANUAL C 8 January 2002...
Страница 73: ...MTEK6000 SERIES USER S MANUAL January 2002 E 3 EL0001 Sheet 1 of 2 Class I Division 2 Installation...
Страница 74: ...MTEK6000 SERIES USER S MANUAL E 4 January 2002 EL0001 Sheet 2 of 2 Class I Division 2 Installation...
Страница 76: ...MTEK6000 SERIES USER S MANUAL F 2 January 2002...
Страница 77: ...MTEK6000 SERIES USER S MANUAL January 2002 G 1 APPENDIX G TII Station Protector...
Страница 78: ...MTEK6000 SERIES USER S MANUAL G 2 January 2002...
Страница 79: ...MTEK6000 SERIES USER S MANUAL October 2002 H 1 APPENDIX H Hazardous Area Installation Control Drawings...
Страница 80: ...MTEK6000 SERIES USER S MANUAL October 2002 H 2...
Страница 81: ...MTEK6000 SERIES USER S MANUAL October 2002 H 3...