MI 3290 Earth Analyser
Technical specifications
133
15.3 Earth Potential [Us]
15.3.1 Potential
Measurement principle: ............................... Current /Voltage measurement
Step and Touch
Measuring range
Resolution
Uncertainty
Us
0,1 V … 199,9 V
0,1 V
calculated value
200 V … 999 V
1 V
Voltage
Measuring range
Resolution
Uncertainty
Um
0,0 mV … 999,9 mV
0,1 mV
(1 % of r 3 digits)
1,000 V … 9,999 V
1 mV
10,00 V … 49,99 V
10 mV
Test mode ...................................................... single
Open-terminal test voltage ........................... 40 Vac
Test frequency ............................................... 55 Hz, 82 Hz, 94 Hz, 105 Hz, 111 Hz, 128 Hz, 164 Hz, 329 Hz
Short-circuit test current ............................... > 220 mA @ 164 Hz
Input resistance (S) ....................................... 1,2 M
Ifault range (selectable) ................................. 1 A … 200 kA
Measuring time ............................................. see Table 15.2 (3 - pole)
Automatic test of probe resistance ............... yes
Automatic connection test ........................... yes [H, S, E]
Automatic range selection ............................ yes
Automatic test of voltage noise .................... yes
Displayed Potential voltage (Us) is calculated as follows:
𝑈
𝑠
= 𝑈
𝑚
∗ (𝐼
𝑓𝑎𝑢𝑙𝑡
/𝐼
𝑔𝑒𝑛
)
15.3.2 S&T Current Source
Measurement principle ................................. Current (MI 3290) / Voltage measurement (MI 3295M)
MI 3290 (current source)
Current
Measuring range
Resolution
Uncertainty
Igen
0,0 mA … 99,9 mA
0,1 mA
(2 % of r 2 digits)
100 mA … 999 mA
1 mA
Test mode ...................................................... continues
Open-terminal test voltage ........................... 40 Vac
Test current frequency .................................. 55 Hz, 82 Hz, 94 Hz, 105 Hz, 111 Hz, 128 Hz, 164 Hz, 329 Hz
Min test current............................................. > 50 mA
Output generator impedance........................ ~ 100 Ω
Test voltage shape ......................................... sine wave
Automatic connection test ........................... yes [H, E]