MI 3100 s, MI 3100 SE
Eurotest
EASI
Appendix D
– Commanders
91
D.4
Operation of commanders
Both LED yellow
Warning!
Dangerous voltage on the commander’s PE
terminal!
Right LED red
Fail indication
Right LED green
Pass indication
Left LED blinks blue
Commander is monitoring the input voltage
Left LED orange
Voltage between any test terminals is higher than 50 V
Both LEDs blink red
Low battery
Both LEDs red and switch off
Battery voltage too low for operation of commander
PE terminal test procedure
Connect
commander to the instrument.
Connect
commander to the item to be tested (see figure D.4).
Touch PE test probe (the
TEST
key) on commander for at least one second.
If PE terminal is connected to phase voltage both LEDs will light yellow, the warning
message on the instrument
is displayed, instrument’s buzzer is activated, and further
measurements are disabled in Zloop and RCD functions.
Figure D.4: Reversed L and PE conductors (application of plug commander)