MI 3100 s, MI 3100 SE
Eurotest
EASI
Safety and operational considerations
10
PE conductor resistance measurement will trip an RCD.
The measurement of PE conductor resistance using trip-lock function does not normally
trip an RCD. However, the trip limit may be exceeded if a leakage current flows to the
PE protective conductor or if there is a capacitive connection between L and PE
conductors.
Autosequence tests (MI 3100 SE)
See notes above for selected tests in Auto-sequence.