MI 3155
Eurotest
XD
Technical specifications
210
12.17
Voltage, frequency, and phase rotation
12.17.1 Phase rotation
Nominal system voltage range ............... 100 V
AC
... 550 V
AC
Nominal frequency range ....................... 14 Hz ... 500 Hz
Result displayed .................................... 1.2.3 or 3.2.1
12.17.2 Voltage / Online terminal voltage monitor
Measuring range (V)
Resolution (V)
Accuracy
0 ... 550
1
(2 % of r 2 digits)
Result type ............................................ True r.m.s. (TRMS)
Nominal frequency range ....................... 0 Hz, 14 Hz ... 500 Hz
12.17.3 Frequency
Measuring range (Hz)
Resolution (Hz)
Accuracy
0.00 ... 9.99
0.01
(0.2 % of r 1 digit)
10.0 ... 499.9
0.1
Nominal voltage range ........................... 20 V ... 550 V