Operation
TWRF1 SCR Power Controller
14
Ametek HDR Power Systems
Rev 2
3.6
On/Off Control
Some applications require that a simple ON/OFF type control be used. The unit can be used in these
simple applications. It can be connected for turn on by a contact closure.
With the TWRF1 configured for non-isolated inputs and the power to the TWRF1 turned off, connect
the system as shown in figure 3.5. A closed contact will turn on (enable) the TWRF1.
Figure 3.5 On/Off Control
Calibrate the system by performing the steps in 3.3. Note that zero power demand is accomplished by
opening the contacts with the controller, and maximum power demand is present when the contacts
are closed.
3.7
Shutdown
When it is necessary to shutdown or disable the output, it is a simple matter. Connect a dry contact
closure between terminals 3 and 4 of the firing circuit as shown in Figure 3.6. A closed contact will
disable the TWRF1 output.
Figure 3.6 Shutdown Control
(Output Disabled By Contact Closure)
WARNING
This method of control is not to be used with isolated inputs
!
Содержание TWRF1 SCR Series
Страница 6: ...Table of Contents TWRF1 SCR Power Controller iv Ametek HDR Power Systems Rev 2...
Страница 8: ...Safety Instructions TWRF1 SCR Power Controller 2 Ametek HDR Power Systems Rev 2...
Страница 12: ...Description TWRF1 SCR Power Controller 6 Ametek HDR Power Systems Rev 2...
Страница 16: ...Operation TWRF1 SCR Power Controller 10 Ametek HDR Power Systems Rev 2...
Страница 22: ...Operation TWRF1 SCR Power Controller 16 Ametek HDR Power Systems Rev 2...
Страница 33: ...TWRF1 SCR Power Controller Appendix Rev 2 Ametek HDR Power Systems 27 Appendix B 30 60 A Outline R...
Страница 34: ...Warranty TWRF1 SCR Power Controller 28 Ametek HDR Power Systems Rev 2 Appendix C 90 225 A Outline R...
Страница 35: ...Notes...
Страница 36: ...530 Lakeview Plaza Blvd Ste C Worthington Ohio 43085 USA...