background image

Configuration & Calibration        

 

47

SECTION 5: 

 Configuration & Calibration of RCT Series with 

Model 275 Communicator without a Device 

Description

 

 

 

 

The Model 275 Communicator can be used to enter and 

download configuration/ calibration values to the RCT 

Series transmitter.

5.1  Range/Span Control

 

 

Definitions: 

•  LRV 

- Lower Range Value of control loop.

•  LSL

 - Lower Sensor Limit corresponding to 

minimum level point. 

•  PV

 - Process Variable; level value from transmitter.

•  SV 

- Secondary Variable; could be volume or 

weight-based on PV. 

•  URV 

- Upper Range Value of control loop. 

•  USL

 - Upper Sensor Limit corresponding to 

maximum level point.

 

 

The first step in configuration is to identify the span 

range position of the instrument.  There is a jumper on 

the back of the electronics chassis:  Range Span 

See Fig. 

3-9

.  The Range Span provides continuous adjustment 

of the change in capacitance required to produce full 

scale current.  Each Range Span position advances the 

range in inches or feet to approximately five times the 

previous setting. Table A-1 gives the range span position 

for a number of common sensing elements and range of 

measurement.

Probe Length Vs. Span Position Number / Maximum Pf

Jumper Position:

  1 

6

Max Pf

 

20 

100  450  2000  10000  40000

 

 

 

 

 

 

 

System 

Maximum Probe Length In Feet

Conducting Liquids

RCTX3XXXXX18 

N/A  N/A  5.4 

20 

N/A 

N/A

RCTX3XXXXX74 

N/A  N/A  9.2 

40 

200 

920

RCTX3XXXXX45 

N/A  N/A  1.2 

5.3 

20 

N/A

RCTX3XXXXX70 

N/A  N/A  1.4 

6.25  31 

140

RCTX3XXXXX40 

N/A  N/A  7.8 

20 

N/A 

N/A

RCTX3XXXXX47 

N/A  N/A  N/A  N/A  4.1 

14

RCTX3XXXXX22 

N/A  N/A  5.4 

20 

N/A 

N/A

RCTX3XXXXX65 

N/A  N/A  5.4 

20 

N/A 

N/A

RCTX3XXXXX72 

N/A  N/A  N/A  4.2 

21 

95

Interface Application

RCTX2XXXXX45 

N/A  N/A  1.2 

5.3 

20 

N/A

RCTX2XXXXX43 

N/A  N/A  1.0 

4.8 

20 

N/A

RCTX2XXXXX47 

N/A  N/A  N/A  N/A  4.0 

14

Insulating K=1.5-5

RCTX2XXXXX22 

N/A  2.7 

12.5  20 

N/A 

N/A

RCTX2XXXXX18 

N/A  8.3 

20 

N/A  N/A 

N/A

RCTX2XXXXX74 

N/A  8.0 

37.5  16 

N/A 

N/A

RCTX2XXXXX45 

N/A  3.6 

16.2  20 

N/A 

N/A

RCTX2XXXXX70 

N/A  3.8 

17.1  76 

N/A 

N/A

RCTX2XXXXX40 

N/A  6.0 

20 

N/A  N/A 

N/A

RCTX2XXXXX43 

N/A  5.0 

20 

N/A  N/A 

N/A

RCTX2XXXXX47 

N/A  5.0 

14 

N/A  N/A 

N/A

Table 5-1

Range/Span 

Setting Chart

Содержание RCT 10 series

Страница 1: ...234 Installation and Operating Instructions RCT 10 11 12 13 Series Transmitter with HART Protocol using 409 T Electronics U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 2...

Страница 2: ...n this manual including but not limited to implied warranties or fitness for a particular purpose Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages...

Страница 3: ...0 111 RCT 10 11 12 13 LM Issue 6 205 Keith Valley Road Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook...

Страница 4: ......

Страница 5: ...3 4 Installing The RS232 Modem 20 3 4 1 Installing The USB Modem 21 3 5 Install the Windows Version HARTWin 2 1 Software on Hard Drive 22 3 6 Description of Function Keys 22 3 7 Configuration 24 3 7...

Страница 6: ...Device 61 6 4 Rosemount Model 275 Calibrator with Device Description Cannot Identify or Find Device 61 6 5 RCT Series Transmitter Does not Communicate with Drexelbrook PC software 62 6 6 Troubleshooti...

Страница 7: ...er from Menu screen 24 Figure 3 5 Level Configuration from Menu screen 24 Figure 3 6 Vessel Configuration from Menu screen 25 Figure 3 7 LRV URV Configuration from Menu screen 25 Figure 3 9 Range Span...

Страница 8: ...SECTION 1...

Страница 9: ...t RCT Series employs a radio frequency signal and adds the Cote Shield circuitry within the Electronics Unit Built in oscillator buffer and chopper drive circuits permit separate measurement of resist...

Страница 10: ...700 0008 122 7 1 700 0008 124 Hast C 7 2 700 0008 126 CS 7 3 700 0008 126 316SS 7 4 700 0008 134 7 5 700 0008 136 7 6 700 0008 144 7 7 700 0008 144 91 77 7 8 700 0008 144 91 299 7 9 700 0008 174 CS 7...

Страница 11: ...3 8 F 700 0002 054 8 G 700 0002 061 8 H 700 0002 062 8 I 700 0002 063 8 J 700 0002 064 9 0 700 0001 034 9 1 700 0001 040 9 2 700 0001 044 9 3 700 0001 045 9 4 700 0001 324 9 5 700 0002 027 90 635 9 6...

Страница 12: ...conducting liquids and granulars 700 5 18 X covered cable Cable 5 16 OD 3 4 NPT 100o F 1000 PSI 250o F 500 PSI 42 Heavy duty for abrasive granulars 700 5 19 Urethane covered cable Cable 3 4 OD 2 NPT 1...

Страница 13: ...ated T4 and may not be used with materials with an auto ignition temperature of less than 135C Substitution of components may impair intrinsic safety To prevent ignition of flammable or combustible at...

Страница 14: ...the electronic unit Figure 2 1 Recommended Conduit Connection WRONG CORRECT CONDUIT BREATHER DRAIN WRONG CORRECT Allows Moisture Infiltration Use only cable supplied by AMETEK Drexelbrook All conduit...

Страница 15: ...stream of a filling nozzle or chute If this is not possible a deflecting baffle should be installed between the sensing element and the fill C Do not take the sensing element apart or loosen the pack...

Страница 16: ...TOO SMALL OR LENGTH TOO LONG DAMAGE MAY OCCUR HERE DAMAGE MAY OCCUR HERE PROBE MAY FLEX INSIDE PIPE FILL LINE AVOID FILL STREAM WALL BUILD UP TOUCHES SENSOR STILLING WELL LACKS VENT HOLES Figure 2 3...

Страница 17: ...ground rod can be fabricated out of any metal compatible with the process Use material that is at least 3 8inch dia such as pipe All Thread or tubing The ground rod must be parallel and relatively cl...

Страница 18: ...AD SHD Three Terminal Sensing Element Shield Wire Red Two Terminal Sensing Element Center Wire Blue Shield Wire Red to be cut by field installer Center Wire Blue To Signal To Signal 1 All devices must...

Страница 19: ...element Use of other cables can result in unstable performance 2 5 Wiring the Sensing Element CAUTION Before using Intrinsic Safety Barriers read manufacturer s instruction for barrier operation The 4...

Страница 20: ...to the probe connection on the transmitter D Connect the shield connector Red of the spark protector to the shield sh connector on the transmitter Figure 2 9 Spark Protection for Integral Sensing Elem...

Страница 21: ...sensing element side or loop side of the unit Unless the assembly is attached to a metallic vessel chassis of transmitter is not grounded 2 7 Surge Voltage Lightning Protection Optional surge protect...

Страница 22: ...ty contact the Drexelbrook Applications department for a recommendation For remotely mounted electronic units connect the sensor to the electronic unit by placing the coaxial cable in grounded metal c...

Страница 23: ...talkies that are used 3 feet 1M or more from a typical electronic unit If greater protection is required or filters have already been provided install RFI filters as shown in Figure 2 12 CE Mark Cert...

Страница 24: ...static filter Drexelbrook Part Number 385 0028 004 as shown in Figure 2 13 2 10 Digital Integral Meter An optional digital integral meter DIM 401 44 3 can be used with the RCT Series electronic unit f...

Страница 25: ...ew location remount meter in new orientation The meter is not inserted into the 4 20 mA loop It receives power and data directly from the Drexelbrook smart transmitter via attached mini ribbon cable S...

Страница 26: ...SECTION 3...

Страница 27: ...are Package includes Contents in 401 0700 021 HART 6 0 DOS version on a 3 Floppy Disk and HARTWin version 2 1 or greater on a CD ROM 4X 1 PC Software Package includes USB Modem Assembly 401 0700 007 F...

Страница 28: ...nstall the hardware that is necessary to run the PC software A Connect the RS232 Drexelbrook Modem 401 700 004 to one of the COM serial ports COM1 COM2 etc of the computer B Connect the Modem s 4 20 l...

Страница 29: ...etup where D is the letter representing the CD Drive Be Sure to Select the USB interface in the setup prompt Follow any On Screen Instructions C Connect the Drexelbrook Modem 401 700 007 to a USB port...

Страница 30: ...function button G The next view shown in Figure 3 3 appears automatically displaying current transmitter database for calibration set up for your selected Tag ID The Scratch Pad will automatically sho...

Страница 31: ...transmitter using Point calibration See Section 3 8 Calibration Enter the low point and high point of level for an accurate calibration D A Trim Allows a field reference meter to be connected to the...

Страница 32: ...e Analog Loop Assign selection box Press Tab or Enter on your keyboard Level configuration sets the output to follow the level of the material being measured Vessel configuration sets the output to fo...

Страница 33: ...orizontal cylinder with dished ends HrzCy Ds Horizontal cylinder with hemispherical ends HrzCy Hm Spherical Sphere The default is Vertical Press Enter and choose the type of vessel D Click on Write to...

Страница 34: ...the PC menu screen It is permissible or sometimes even recommended that both methods be used in order to establish a calibration standard For example if the vessel was already filled before the calibr...

Страница 35: ...er Position 1 2 3 4 5 6 Maximum pF 20 100 450 2000 10000 40000 System Maximum Sensing Element Length In Feet Conducting Liquids RCTX3XXXXX18 N A N A 5 4 20 N A N A RCTX3XXXXX74 N A N A 9 2 40 200 920...

Страница 36: ...ter A Go to Level Calibration area of the menu B Enter Lower Level value Press Tab or Enter C Enter Lower Capacitance value Press Tab or Enter D Enter Upper Level value Press Tab or Enter E Enter Uppe...

Страница 37: ...igh Point 16 feet Hi Cal URV 1185 gallons 20 mA Maximum Level 20 feet Maximum Capacity 1200 gallons LRV may either reference the bottom of the vessel bottom of the sensor or an elevated point on the s...

Страница 38: ...estimated 100 capacitance value is less than 10 of the maximum pF for the range below the selected range Example A unit in Range Span 4 2000 pF projects maximum capacitance equal to 400 pF Action Low...

Страница 39: ...a 2 point to 21 point table used by the RCT Series to cause the output current to follow a specified relationship to the level There are certain strapping tables that are already built in to the tran...

Страница 40: ...9 90 20 95 21 100 By clicking on Last Read Values this view may also be used to review existing strapping tables previously entered A Plan your table by filling out table 3 2 You may use the first col...

Страница 41: ...set the meter display range equal to percent of level Minimum Value 0 Maximum Value 100 When a smart transmitter is powered down or the ribbon cable is disconnected there is a 1 minute delay before t...

Страница 42: ...maximum capacitance values are known and remain unchanged the effects of a specific capacitance value within this range can be accurately predicted If a known capacitance which can be NIST traceable...

Страница 43: ...d The Loop Current and the Percentage will also reflect the values that are generated by the NPO Capacitor Add to the scratch pad of the Menu Screen the value of the NPO capacitor that you used If des...

Страница 44: ...In Percent Out Percent 0 00 0 00 o oo 0 00 1 00 5 00 60 00 5 00 2 00 10 00 120 00 10 00 3 00 15 00 180 00 15 00 4 00 20 00 240 00 20 00 5 00 25 00 300 00 25 00 6 00 30 00 360 00 30 00 7 00 35 00 420 0...

Страница 45: ...Lower Cap Enter View Lower Level View Lower Cap Enter Up Down Return Up Down Up Down Enter Enter Enter Enter Enter Enter Upper Level Upper Cap Enter Edit 0 99900 Edit 0 99900 Enter Up Down Enter Upper...

Страница 46: ...SECTION 4...

Страница 47: ...llowing steps Turn on the calibrator From the top screen push 1 Offline Push 1 New Configuration A Table of Contents is shown that lists all the Manufacturers in alphabetical order Drexelbrook is thir...

Страница 48: ...mitter terminals must be at least 12 volts with 20 mA of loop current Other possible loop devices such as a setpoint controller Optional Safety Barrier HART Compatible 4 2 Start up After the RCT Serie...

Страница 49: ...NU 3 BASIC SETUP 4 DETAILED SETUP 5 REVIEW UNIV III TAG STATUS 1 UNIV III STATUS UNIV III TAG UNIV III STATUS SPAN TOO SMALL AAAAA DECREMENT SPAN AAAAA INCREMENT SPAN AAAAA OVERRANGE AAAAA UNDERRANGE...

Страница 50: ...el Config Edit all values as done for Level Config Select Exit and proceed to 4 4 Calibration 4 4 Calibration There are two methods of calibrating the RCT Series transmitter Point Calibration or Capac...

Страница 51: ...ration Continued it would be best to use a calculated zero capacitance for the low point and actual level for the high point While this wouldn t be as accurate as two known level points it will be rea...

Страница 52: ...and application information to the Service Engineer Following is the keystroke sequence for Capacitance Calibration using the Model 275 Calibrator Select Device Setup Select Configuration Menu Select...

Страница 53: ...T AS A PERCENT OF MAXIMUM CAPACITY XXX XXX UNIV III Tag POINT NUMBER X ENTER INPUT LEVEL VALUE XXX XXX UNIV III Tag POINT NUMBER X ENTER OUTPUT CAPACITY VALUE XXX XXX UNIV III Tag POINT NUMBER X ENTER...

Страница 54: ...les are automatically created by selections made with Vessel Config assignment during Configuration procedure in Section 4 3 If output to level relationship is not defined by one of these tables you m...

Страница 55: ...ches or feet to approximately five times the previous setting Table A 1 gives the range span position for a number of common sensing elements and range of measurement Probe Length Vs Span Position Num...

Страница 56: ...r Function Keys The function keys F1 through F4 indicate the specific actions that are available to complete the software function The action words that appear above each key change as you move throug...

Страница 57: ...Configuration Calibration 49 5 4 Set Up Procedures...

Страница 58: ...RCT 10 11 12 13 Series 50 5 4 Set Up Procedures Continued...

Страница 59: ...Configuration Calibration 51 5 4 Set Up Procedures Continued...

Страница 60: ...b 1 DEVICE SETUP c 4 DETAILED SETUP d 1 SENSORS e 1 PV f view Process Variable g EXIT F4 h HOME F3 or a select the ONLINE MAIN menu b 2 PV c view Process Variable d F4 EXIT e 2 PV f 3 PV AO g view An...

Страница 61: ...RV 2 PV URV 3 PV USL 4 PV LSL Choose PV LRV if your vessel currently has a low level Choose PV URV if your vessel currently has a high level Edit the displayed value to equal the actual tank level the...

Страница 62: ...V 2 PV URV 3 PV USL 4 PV LSL Choose PV LRV if performing a low point calibration Choose PV URV if performing a high point calibration Edit the displayed value to equal the actual tank level then ENTER...

Страница 63: ...g Horizontal Cylinder Other Other Installation Details NPT Thread Mount Flange Mount if flange mount B inches E A inches H inches D inches H inches IL inches Unless specified otherwise calibration val...

Страница 64: ...atter They can be done at different times 5 8 2 Selecting Engineering Units The examples in this procedure use the default units of feet For other units use the following procedure A Connect the handh...

Страница 65: ...e at 100 exceeds the present capacitance range jumper setting Example For 0 to 10 ft calibration span select jumper 100 pF point cal LRV 0 ft 10 pF URV 7 ft 90 pF generates this error because the proc...

Страница 66: ...SECTION 6...

Страница 67: ...tic output jumps around noticeably in terms of seconds or minutes Test Transmitter Check process level Check for Static Discharge Check for radio interference 6 6 6 9 6 10 Erratic readings often show...

Страница 68: ...ubleshooting Loop Connection Specific transmitter loop connections will vary from installation to installation but in general will be connected in a similar manner to typical transmitter loop in Figur...

Страница 69: ...ter than 22 mA disconnect at sensing element and re check If current returns to normal check sensing element using checkout procedure in Section 5 7 If current does not return to normal test transmitt...

Страница 70: ...urrent does not return to normal test transmitter with procedure in Section 5 6 2 If loop current is 0 mA check polarity of loop at transmitter If it is OK check for open loop 3 If loop current is bet...

Страница 71: ...ansmitter from PROBE to GND ground terminals See Figure 6 1 5a Using a PC Using the real time view F4 verify that the displayed capacitance value is within the value and tolerance printed on the test...

Страница 72: ...4 mA 120 pF 20 mA 800 pF 800 pF 120 pF 680 pF 680 pF 2 340 pF 7 Adjust the capacitance box C box to the number figured in step 6 The signal should read approximately 50 8 If the display reads 50 the u...

Страница 73: ...which is required to detect a pinhole or crack in the sensing element insulation In addition digital meters frequently give erroneous results due to a battery like effect when dissimilar metals conta...

Страница 74: ...ng Element Step 2 Figure 6 6 Raise the level in the vessel to cover as much of the sensor as possible Repeat the measurement made in step 1 Readings of 1 meg ohm or less indicate a pinhole or crack in...

Страница 75: ...onductors Note any reading Repeat for all three conductors All readings should show an open circuit infinite resistance SHORT OUT TWO CONDUCTORS CENTER GROUND CENTER SHIELD SHIELD GROUND OHMS OHMS OHM...

Страница 76: ...k transmitters have a significant amount of RFI protection built in There are situations however where the standard protection is inadequate RFI filters are available to provide additional protection...

Страница 77: ...g difficult application problems or in plant training of personnel Contact the service department for further details 6 13 Customer Training Periodically AMETEK Drexelbrook instrument training seminar...

Страница 78: ...27 6297 US and Canada or 215 674 1234 International Please provide the following information Model Number of Return Equipment Serial Number Original Purchase Order Number Process Materials to which eq...

Страница 79: ...ent Percentage Status Press F4 For Real Time View Type 00 30 LRV 4mA URV 20mA Vessel Sketch Show principal tank dimensions including vessel construction mounting location nozzle LRV URV present level...

Страница 80: ...SECTION 7...

Страница 81: ...emperature Effect 1 of range per 50 F 30 C Supply Voltage Effect 0 1 from 12 to 30 VDC Effect of Load Resistance 0 1 for full resistance range at 24 VDC supply Response to Step Change 1 second standar...

Страница 82: ...s Nonincendive Equipment Class I Div 2 Groups A B C and D Class II Div 2 Groups E F and G Class III Div 2 Sensing Element Cable Length 100 feet maximum 7 2 Coaxial Cable Specifications General Purpose...

Страница 83: ...e may be required for harsh environments See Note 1 7 4 Approvals Available Note 1 Always Install to Local Codes Requirements Directives as Mandated by the Authority Having Jurisdiction Note 2 For app...

Страница 84: ...v 2 Groups A B C and D Class II Div 2 Group E F and G Class III Class I Zone 2 Ex na IIC For Ambient temperatures above 70 C use wiring rated 75 C or higher Intrinsically Safe Class I II III Div 1 Gro...

Страница 85: ...1 Viewport Cleaning The viewport if supplied is made of Borosilicate glass and can be cleaned with any common glass cleaning product e g Windex Isopropyl alcohol etc that is suitable for the Class and...

Страница 86: ...APPENDIX A...

Страница 87: ...Appendix A A 1 APPENDIX A APPROVAL DRAWINGS A 1 ATEX APPROVAL DRAWINGS...

Страница 88: ...RCT 10 11 12 13 Series A 2 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 89: ...Appendix A A 3 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 90: ...RCT 10 11 12 13 Series A 4 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 91: ...Appendix A A 5 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 92: ...RCT 10 11 12 13 Series A 6 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 93: ...Appendix A A 7 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 94: ...RCT 10 11 12 13 Series A 8 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 95: ...Appendix A A 9 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 96: ...RCT 10 11 12 13 Series A 10 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 97: ...Appendix A A 11 A 1 ATEX APPROVAL DRAWINGS Continued...

Страница 98: ...RCT 10 11 12 13 Series A 12 A 2 CSA APPROVAL DRAWINGS...

Страница 99: ...Appendix A A 13 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 100: ...RCT 10 11 12 13 Series A 14 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 101: ...Appendix A A 15 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 102: ...RCT 10 11 12 13 Series A 16 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 103: ...Appendix A A 17 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 104: ...RCT 10 11 12 13 Series A 18 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 105: ...Appendix A A 19 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 106: ...RCT 10 11 12 13 Series A 20 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 107: ...Appendix A A 21 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 108: ...RCT 10 11 12 13 Series A 22 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 109: ...Appendix A A 23 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 110: ...RCT 10 11 12 13 Series A 24 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 111: ...Appendix A A 25 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 112: ...RCT 10 11 12 13 Series A 26 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 113: ...Appendix A A 27 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 114: ...RCT 10 11 12 13 Series A 28 A 2 CSA APPROVAL DRAWINGS Continued...

Страница 115: ...Appendix A A 29 A 3 FM APPROVAL DRAWINGS Continued...

Страница 116: ...RCT 10 11 12 13 Series A 30 A 3 FM APPROVAL DRAWINGS Continued...

Страница 117: ...Appendix A A 31 A 3 FM APPROVAL DRAWINGS Continued...

Страница 118: ...RCT 10 11 12 13 Series A 32 A 3 FM APPROVAL DRAWINGS Continued...

Страница 119: ...Appendix A A 33 A 3 FM APPROVAL DRAWINGS Continued...

Страница 120: ...RCT 10 11 12 13 Series A 34 A 3 FM APPROVAL DRAWINGS Continued...

Страница 121: ...Appendix A A 35 A 3 FM APPROVAL DRAWINGS Continued...

Страница 122: ...RCT 10 11 12 13 Series A 36 A 3 FM APPROVAL DRAWINGS Continued...

Страница 123: ...Appendix A A 37 A 3 FM APPROVAL DRAWINGS Continued...

Страница 124: ...RCT 10 11 12 13 Series A 38 A 3 FM APPROVAL DRAWINGS Continued...

Страница 125: ...Appendix A A 39 A 3 FM APPROVAL DRAWINGS Continued...

Страница 126: ...RCT 10 11 12 13 Series A 40 A 3 FM APPROVAL DRAWINGS Continued...

Страница 127: ...Appendix A A 41 A 3 FM APPROVAL DRAWINGS Continued...

Страница 128: ...RCT 10 11 12 13 Series A 42 A 3 FM APPROVAL DRAWINGS Continued...

Страница 129: ...Appendix A A 43 A 3 FM APPROVAL DRAWINGS Continued...

Страница 130: ...RCT 10 11 12 13 Series A 44 A 3 FM APPROVAL DRAWINGS Continued...

Страница 131: ...A 3 FM APPROVAL DRAWINGS Continued...

Страница 132: ...not transfer any intellectual property rights to Buyer unless Seller specifically agrees to do so in writing Seller shall retain ownership of all applicable patents trademarks copyrights and other int...

Страница 133: ......

Страница 134: ...d Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook info ametek com Website www drexelbrook com An ISO 90...

Отзывы: