Battery operation
Whad 1500 Whad 2000 Whad 2500
Applied load in percentage
50
% 80 % 50 % 80 % 50 % 80 %
Approximate autonomy in minutes with
27
15 22 10 16 8
charged batteries
Recharge time up to 90% of total load
5-6 hours according to level of discharge
Technical data and quantity of batteries
N° 6 pcs 12V 7Ah sealed
N° 3 pcs 12V 7Ah, sealed, lead-acid,
lead-acid, maintenance free maintenance free batteries connected in
connected in series series for each powerboard
Reserve signal
From 32.2V to 36V can be programmed by operator
Minimum voltage for battery operation
From 27V to 31.5V with automatic selection according to
load or can be programmed by operator
Average battery life
3-6 years according to use and working temperature
Warning !
The batteries in the UPS are subject to a reduction in
capacity according to their age (a feature of lead batteries
declared by their manufacturer in the technical manual). For
example, the reduction in the capacity of a 4-year-old battery
can reach 40% with a proportional reduction of autonomy
times of the UPS when operating in battery mode.
Bypass Specifications
Type of bypass
Electro-mechanical
Standards
Safety
Conforms to standard EN 62040-1-1
Electromagnetic compatibility:
Immunity - emission
Conforms to standard EN 50091-2
Performance and features
Conforms to standard EN 62040-3