18
Output wave form
Whad 1500 Whad 2000 Whad 2500
With mains operation
Sinewave
With battery operation
Sinewave
Type of operation
No break, on line UPS with passing neutral and double
conversion
Electrical output specifications with mains operation
Nominal output voltage
230V +/-1%
Nominal output frequency
50Hz / 60Hz synchronised
Output current with linear load P.F.=0,7 6,6 Arms 8,7 Arms
10,86 Arms
Tolerated crest factor on output
3,5
current
Nominal output power
1500 VA
2000 VA
2500 VA
Active output power with linear or
1050 W
1400 W
1750 W
non-linear load PF = 0.7
Total harmonic distortion of output voltage
< 0,5%
with linear load
Total harmonic distortion of output voltage
< 1%
with non-linear load P.f.=0,7
Overload capacity
300% for 1 second without bypass intervention
200 % for 5 seconds without bypass intervention
Power factor range with applied load
From 0,7 to 1
Number of output phases
Single phase
AC-AC conversion efficiency with linear load
PF = 1 and charged batteries
With 50% load
80%
With 75% load
84%
With 100% load
90%
Electrical output specifications with battery operation
Nominal output voltage
230V +/-1%
Output frequency
50Hz/60Hz +/-1%
Nominal output power
1500 VA
2000 VA
2500 VA
Active output power with linear or
1050 W
1400 W
1750 W
non-linear load PF = 0.7
Total harmonic distortion of output voltage
< 1%
Overload capacity
200% for 15 sec.
160% for 15 seconds
Power factor range tolerated with
from 0,7 to 1
nominal load
DC-AC conversion efficiency with linear load
PF = 1 and charged batteries
With 50% load
80%
With 75% load
80%
With 100% load
80%
V81608A Ist.Uso Whad2000:V81608A Ist.Uso UPS Whad2000 8-04-2008 9:52 Pagina 18