20 Notification Appliances—CH Series Chimes and Strobe Chimes
2.
Connect the signaling device to the backbox using the lock washer (provided in the
hardware bag) under the head of each mounting screw.
Refer to Figures 8 and 11 when wiring chimes only.
Figure 11: Chimes Wiring Diagram
Refer to Figures 9 and 12 when wiring the device to operate the chime signal and strobe
independently. Johnson Controls recommends this method for coded systems where the
chime is set on Single Stroke (SS) and is cycled on and off while the strobe flashes
continuously.
Figure 12: Strobe and Chime Operate Independently
Chimes
F ro m P re ce din g
S igna l or F ire A larm C o ntrol P ane l
(F A C P )
T o N ext
S ignal or E nd-of-Line R esistor
(E O LR )
c hm w ire 1
+
-
+
-
+
-
G roun d
Strobe Chimes
From P receding
S trob e or FA C P
s tro b w r1
G round
S trobe
(O ptional)
Ch im e
From P receding
S peaker or Fire A larm
C ontrol P anel (FA C P)
T o N ext S trobe
or E O LR
T o N ext S peaker
E nd-O f-Line Resistor
(E O LR )
+
-
+
-
+
-
+
-
+
-
+
-