Closable air supply vents with cable controls can be purchased from Metalfire.
Safety zone from flammable materials
Appliance without convection mantle
The combustion air supply must be installed as
depicted in the sketches shown previously.
The air supply from the room enters the fireplace via
opening(s) at the bottom of the surround.
The heated air in the room flows through the
opening(s) at the top of the surround back into the
room. The air supply opening at the bottom and top
must both be at least 700 cm². If there is a grate, the
net throughput (throughput coefficient) must be
taken into account. The openings at the top must be
30 cm lower than the ceiling.
Combustion air
supply from
outside
Flue gas
discharge
Heated
air in the
room
Room air to
fireplace surround
The heat radiation through the fireplace
window can be considerable. Therefore,
a distance of at least 80 cm must be
kept from flammable material.