  Feed time 

Feed time in SUPERVISION mode; too high value may cause the boiler 
to  overheat  or  fuel  over-filling;  too  low  value  results  in  fuel  returning  to 
the container. 

  Interval time 

Feeder work cycle time in Supervision mode. 

SUPERVISION cycle time 

= feed time 

interval time 

 

  Fan time extension 

In  SUPERVISION mode,  after  a  fuel  dose is supplied and  the  feeder is 
off,  the  continues  to  work  for  the  extension  period  in  order  to  ignite  the 
fuel dose. This parameter should not be set too high as it may over heat 
the boiler. 

Min. fan speed  

Minimal fan speed in % that can be selected by the user of the regulator. 
This  parameter  is  used  to  limit  the  access  to  the  complete  fan  speed 
range  in  the  user  menu.  It  is  not  used  in  the  fan  control  algorithm.  The 
parameter  should  be  set  relatively  low,  allowing  the  fan  to  spin  slowly 
and freely. 

Lack of fuel detection time 

 

Lack  of  fuel  detection  time  is  deduced  after  the  exhaust  temperature 
drops  below  the 

Lack  of  fuel  detection  threshold. 

After  this  time  is 

deduced, the regulator makes 3 attempts to ignite the burner, and when 
this fails, it displays the “ignition failed” alarm. 

Exhaust temperature when no 
fuel 

If exhaust temperature is lower than this value for a time longer than the 
time  set  in  the 

Fuel  lack  detection  time

  parameter,  lack  of  fuel  will  be 

detected and next firing-up attempt will be made. 

Exhaust temperature increase 
time 

This  time  is  used  as  function  preventing  the  extinguishing  of  flame  in 
OPERATION  mode.  If  the  exhaust  temperature  does  not  exceed  the 

Lack of Fuel Detection threshold

 after such time, an ignition test will be 

made. 

Exhaust temperature - blow 
reduction 

Exhaust  temperature  over  which  revolutions  of  the  fan  are  reduced 
(down to a minimum power). 

Max. feeder temp.  

This parameter determines the maximum temperature at which the alarm 
for exceeding the maximum feeder temperature is displayed. When this 
temperature  is  exceeded,  the  feeder  is  engaged  for  a  predefined  time, 
with  a  several-minute  pause.  If  the  temperature  drops,  the  regulator 
resumes normal operation; if not, the feeder will be engaged for a longer 
period  in  order  to  remove  embers  from  the  feeding  pipe.  These  times 
may be edited in a special menu accessible only to the manufacturer of 
the boiler. 

Feeder 2 operation time 

Additional (external) feeder operation time. 

14.2

 

BOILER 

 

Grate

 

 

 

Max. ignition time 

When  this  time  is  exceeded  ant  the  exhaust  temperature  does  not  rise 
above the Lack of Fuel detection thr15°C, a failed ignition alarm 
will be displayed.  Note: during ignition in RUST mode, the fan works at 
the 

Ignition  fan  -  grate

  speed.  This  parameter  is  adjusted  via  the  user 

menu. 

 

Lack of fuel detection time 

Time is counted after fumes temperature drops below the 

Fuel detection 

threshold

  value.  In  the  grate  mode,  blow  operation  is  stopped.  If  the 

burner is active, flame test is started. Lack of fuel detection is off for "0" 
setting. 

 

Lack of fuel detection method 

Only  exhaust  -  lack  of  fuel  detection  occurs  via  the  indications  of  the 
exhaust  temperature  sensor.  This  method  allows  to  detect  the  lack  of 
fuel quickly. It can only be used when there is an exhaust sensor in the 
flue of the boiler.  
Water and exhaust - lack of fuel detection occurs both via the indications 
of the exhaust temperature sensor and the water temperature sensor in 
the  boiler.  To  detect  the  lack  of  fuel,  both  temperatures  need  to  drop, 
and  the  water  temperature  in  the  boiler  must  drop  below  the 

CH  pump 

activation temperature

 

Boiler hysteresis 

If  boiler  temperature  goes  below  preset  temperature  by  value  of  boiler 
hysteresis, then automatic firing-up of burner takes place. 

 

Purge operation - supervision 

Fan  purge  time  when  the  boiler  temperature  exceeds  the  boiler’s  set 
temperature  

 

Purge interval - supervision 

Fan purge interval time when the boiler te

mperature exceeds the boiler’s 

set temperature 

Содержание ecoMAX860P TOUCH

Страница 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Страница 2: ......

Страница 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Страница 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Страница 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Страница 6: ...6...

Страница 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Страница 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Страница 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Страница 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Страница 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Страница 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Страница 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Страница 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Страница 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Страница 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Страница 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Страница 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Страница 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Страница 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Страница 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Страница 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Страница 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Страница 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Страница 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Страница 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Страница 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Страница 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Страница 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Страница 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Страница 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Страница 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Страница 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Страница 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Страница 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Страница 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Страница 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Страница 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Страница 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Страница 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Страница 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Страница 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Страница 43: ......

Страница 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Отзывы: