The installation may be equipped with the following safety devices. Refer to the product
specifications in Section 5 for the installed devices.
Roll-off / fall protection / slack cable protection / pinch protection / switching
protection.
Smoke and temperature detectors and/or fire alarm system (BMI).
Shielding below 2500 [mm] from an accessible floor, mandatory in case of a crushing
hazard (NEN-EN 294).
ATEX components, if used in potentially explosive atmospheres.
3.2
Safety instructions
The fire shutter door is designed in such a way that the door will always close in case
of fire or a smoke alarm. The possible presence of persons is therefore not taken into
account. (Exceptions to this are possible in consultation with or after approval by the
competent authority; the installing party or (end) user must arrange this approval.)
If the door is installed in an escape route, ensure that the door is suitable for its
intended use (escape door). (EN 16034-2) (EN 14351-1 and 2)
When using a deadman’s control system, the control switch must be positioned in
such a way that the operator has a clear view of the opening/closing of the door.
Before operating, check that there is no visible damage to the door. If any damage is
found, the supplier must be asked to repair the damage. A door that is damaged
must not be operated.
During operation, check that there are no persons within ±2 [m] of the door.
The door may only be operated by persons who have familiarised themselves with
the operating instructions. Under no circumstances shall the door be operated by
children or persons with an impaired physical, sensory or mental condition. The door
may only be used in the manner described in paragraph 4.1.
Check that there are no obstacles under the roller shutter when closing.
During maintenance/inspection of the fire door, the system must be powered down.
Avoid trapping persons in the room. If anyone is still present, the door must remain
open.
If a failsafe drive is used, the door will close when the mains power and any back-up
battery are switched off; if the back-up battery is not switched off, the door will close
when the critical voltage is reached.
The entire installation should preferably be earthed (guide and bracket plates); this is
mandatory for an ATEX model.