A. Room Terminators (Outlets): Based on the equipment
selected, determine the recommended number of
fully open outlets from Figure 3.1.
FIGURE 3.1
NOMINAL
TONNAGE
2
2-1/2
3
3-1/2
4
5
MODEL
ESP-2430JV
ESP-2430JV
ESP-3642JV
ESP-3642JV
ESP-4860JV
ESP-4860JV
A
12
15
18
21
26
30
MINIMUM RECOMMENDED
NUMBER OF FULLY OPEN OUTLETS
B
14
18
21
25
28
35
5. Check that system static pressure is within acceptable
limits (minimum 1.2" WC - ,maximum 1.5" WC). You
can use a U-tube manometer to check the external sta-
tic pressure on the duct system.
1. Puncture a ¼" diameter hole in the plenum duct at
least 18" from the fan coil unit.
2. Insert the high-side manometer tube into the hole so
that the end is approximately flush with the inside wall
of the plenum, and perpendicular to the direction of airflow.
3. System static pressure should be between 1.2" and 1.5" WC.
a. If the pressure is higher than 1.5" provide additional
supply runs to increase airflow or lower the fan
speed by turning the fan speed adjustment for the
current mode of operation counter-clockwise to
reduce the static pressure.
b. If the pressure is lower than 1.2", look for leaks in
the supply plenum, restrictions in the return system
(including clogged filters) If more than the
recommended number of supply runs are installed,
you may install flow restrictors (orifices) in these
runs. If the number of runs is appropriate for the
load, increase the static pressure by turning fan
speed adjustment for the current mode of operation
clockwise to increase the static pressure.
6. Check that blower motor amp draw compares with
fan coil unit rating plate. Amp draw shown on plate is
the FLA of motor (not the actual running amps) and will
vary with the pressure and voltage.
7. Place the thermostat cooling indicator in COOL position,
which will start the outdoor unit. Let the system run at
least 30 minutes to stabilize operating conditions.
8. For outdoor unit start-up, follow manufacturer’s instructions.
9. Check that temperature drop across evaporator coil
in the indoor unit is between 20°F to 28°F.
NOTICE: Do not introduce refrigerant liquid to system
through suction port. Liquid in the suction line may
damage the compressor.
NOTICE: Before adding refrigerant to system verify
Item #5 in “System Start-up & Adjustment” section
has been performed.
10. Verify that system refrigerant is correct by measuring
subcooling at liquid service port. Subcooling should be
in accordance with outdoor unit manufacturers
recommendations..
11. Check the super heat leaving the evaporator coil
against the corresponding suction pressure from the
schrader fitting at the fan coil unit. Superheat value
should be between 9°F and 12°F.
12. If a sight glass has been installed on the liquid line at
the air handler check for the presence of flashing. If
flashing is occuring, check and adjust subcooling by
adding refrigerant.
ChARGING COOLING ONLY SYSTEMS
After start-up, allow the system to operate for
approximately 30 minutes in order to establish stable
operating conditions. Check that the temperature drop
across the evaporator coil is 20°F to 30°F. Do not attempt
to adjust the charge at ambient temperatures below 65°F.
Verify and adjust refrigerant charge based upon outdoor
unit manufacturer’s published recommendations.
Releasing refrigerant gas into the atmo-sphere is a
criminal offense.
FACTORS AFFECTING ThE BALANCE OF ThE SYSTEM
1. The minimum or recommended number of outlets
means fully open outlets. Any outlet having an orifice
would be only a percentage of an outlet.
2. For systems with average supply tubing lengths of 15
feet or less, use column A. For systems with supply tubing
lengths greater than 15 feet, use column B.
NOTICE: The number of outlets and average length of
the supply tubing has a significant effect on the overall
system performance. It is highly recommended that the
adjustment factors outlined in the SpacePak Application
Manual are accounted for prior to any installation.
B. Orifice Combinations: Should orifices be required to
balance the system (installed at plenum take-off),
refer to the combinations listed in Figure 3.2
Содержание SpacePak ESP-2430JV
Страница 11: ...11 FIGURE 2 9 MODEL ESP JV STANDARD WIRING SChEMATIC ...
Страница 12: ...FIGURE 2 10 SINGLE STAGE AIR CONDITIONING ONLY WIRING DIAGRAM 12 ...
Страница 13: ...13 FIGURE 2 11 SINGLE STAGE AIR CONDITIONING WITh hW COIL WIRING DIAGRAM ...
Страница 14: ...14 FIGURE 2 12 TWO STAGE hEAT PUMP AC WIRING DIAGRAM ...
Страница 15: ...15 FIGURE 2 13 TWO STAGE hEAT PUMP AC WITh BACKUP BOILER hEAT WIRING DIAGRAM ...
Страница 33: ...33 NOTES ...
Страница 34: ...NOTES ...
Страница 35: ...35 ...