Mestek Kickspace Series Скачать руководство пользователя страница 6

6.

1. If Kickspace heater does not turn on check below for possible solutions:

A. Verify the following:

a) Check to see if there is a call for heat

 

•  Turn up thermostat, wait for water to come up to temperature and unit blower/motor should turn on.

b) Verify aquastat is clipped firmly to copper tube. Clip may become loose during shipping. Located under 

    electrical box cover.

c) Check for power switch to be in low or high position

 

•  Switch in front of unit should be switched to the left or right, middle position is off.

d) Check for power to the unit (115v) with voltmeter

e) Check supply piping to see if its hot

 

•  If piping isn’t hot, water is not getting into the kickspace heater check the directional flow tee and   

  piping installation (see pages 4 and 5 for help with tee installation).

2. If above criteria have been verified and unit will still not turn on try the following:
Jumper out (by-pass) the aquastat; this should be done by a licensed electrician.

A. If blower turns on check below for possible solutions:

a) Water is not hot enough

 

•  Check system water temp.  If radiant system, low temperature aquastat may be needed.

b) Water not circulating fast enough

 

•  Kickspace heaters must have at least 1GPM flow to operate properly.  If system circulator is not    

  running kickspace heater will not turn on.

c) Water not getting into kickspace heater (supply line not hot)

 

•  need to check installation piping and directional flow tee arrangement (see pages 4 and 5)

 

•  Possible air problem – bleed air from unit 

d)  Thermostat wired to unit not working properly

e)  Aquastat is not functioning properly 

 

•  Replace aquastat

B. If blower does not turn on:

a) Check all electrical connections

b) Blower motor may be defective

After going through these steps, if the unit still fails to operate, contact your local heating & plumbing contractor.

3. Noisy blower motor:

•  Blower may have shifted during shipping/installation. A screwdriver may be used to push the blower 

away from the motor. Simply insert a screwdriver between blower (end closest to electrical box) and 

blower housing, and gently push blower away from housing.

Kickspace Heater Troubleshooting

Содержание Kickspace Series

Страница 1: ...gh a flush mounted louvered front panel Type F is a surface mounted wall unit with the air discharged evenly through a louvered front panel in an upward direction All types have heating elements with...

Страница 2: ...KICKSPACE MODEL 42 FIGURE 1 2 KICKSPACE MODEL 84 FIGURE 2 KICKSPACE MODEL 120 FIGURE 3 Dimensions shown in English and metric DIMENSIONAL DATA...

Страница 3: ...ATION AND SERVICE IT IS RECOMMENDED THAT THIS ACCESS PANEL BE CONSTRUCTED SO ANNUAL CLEANING OF THE BLOWER FAN AND COIL FINS CAN BE EASILY ACCESSIBLE 3 At this location center and cut an opening in th...

Страница 4: ...erated flow control or circuit setter can be placed between the two standard tee s in a one pipe system For consistent response of the reverse acting thermostat and effective outlet air temperature th...

Страница 5: ...allation Figure 8 is a supply installation Figure 9 shows installation for the return side red ring between risers The return tee is installed opposite of the supply tee with the red ring between the...

Страница 6: ...ower turns on check below for possible solutions a Water is not hot enough Check system water temp If radiant system low temperature aquastat may be needed b Water not circulating fast enough Kickspac...

Страница 7: ...eck valve Do not return to bottom drain tapping Operation from steam boiler water is entirely possible as long as supply and return connection is installed be low level of water line on a steam boiler...

Страница 8: ...anship of any installer of the Product This limited warranty is conditional upon a shipment to the Manufacturer of that part of the Product thought to be defective Goods can only be returned with prio...

Отзывы: