Operating Instructions MBI 46.51.39
Version 0.9
en MBI 46.51.39 operating instructions.docx
Issue: 08/2022
page 19 from 29
5.5 Adjustment of gain range
To match the measuring amplifier with the sensitivity of the sensor, the gain range
be selected
by use of JP1 jumper. Depending on the nominal output signal of the transducer used, the
plug-in bridge is plugged into one of the 4 gain ranges.
Gain Range:
JP1-4: 310 ... 740 mV/V
JP1-3: 130 ... 310 mV/V
JP1-2: 55 ... 130 mV/V
JP1-1: 25 ... 55 mV/V
Figure 118 Setting of Gain Range
5.6 Adjustment of offset, gain and phase-shift
Subsequently, the measuring amplifier can be adapted to the displacement transducer and
the desired output signal by means of trimming potentiometers for fine adjustment. Small
tolerances in the mechanical installation of the transducer can also be compensated.
The precise nominal properties of the measuring amplifier are only achieved after
about 15 minutes of warm-up time.