28
Adjustable parameters
a) Set independently via base unit
For further information see the operating
instructions for the Easy base unit or the
documents for external EIB Easy setting
devices.
Supported functions
b) Adjustable via base
Scene numbers
(for Scene function)
Edge function
(for Edge function)
1)
Factory setting
Push-button
Edge function
Dimming
Blind
Timer mode
Scene
1
1)
2
3
4
5
6
7
8
On -
Off -
On - Off
1)
Off - On
Anleitung_770104.book Seite 28 Dienstag, 15. Oktober 2002 9:12 09
29
Technical data
Bus supply
24 V / I approx. 5 mA
Ambient temperature:
Operation:
Storage:
Transport:
-5 °C to +45 °C
-25 °C to +55 °C
-25 °C to +70 °C
The device is designed for
use at a height of up to
2000 m above sea level
(MSL).
Control element:
Programming key, manual
Display element:
1 red LED:
programming control
1 green Operation-LED:
Operation indicator
4 yellow status-LED´s:
under the labelling field
Connections:
Bus supply terminal via two
1 mm pins
Two triple screw terminals
for max. 2.5 mm
2
Insulation voltage:
4 kV between bus and the
binary inputs
Inputs:
Input voltage
Input current:
Signal interpretation:
Connections:
Length of line:
AC 230 V, 50 to 60 Hz
approx. AC 12 mA
Characteristic of inputs
acc. to IEC65A Type 2
Input voltage 40 V: Off
Input voltage 160 V: On
Every two inputs (E1/E2
and E3/E4) have a shared
an N-connection.
The N-connections have an
internal bridge.
The bridge is not suitable
for carrying a load current.
max. 100 m
Anleitung_770104.book Seite 29 Dienstag, 15. Oktober 2002 9:12 09
30
Device width:
2,5 depth units
= approx. 45 mm
EC Directives:
Complies with low voltage
directive 73/23/EEC
Complies with EMC direc-
tive 89/336/EEC