2

V

Hazardous voltage. 

Will cause death or serious injury.

KEEP OUT.

Qualified personnel only.

Disconnect and lock off all power before working 

on this equipment.

V

DANGER

Figure 2

Dimensions & Weight

Device Operation

SPDs sense overvoltage conditions and create a momentary 
short circuit to redirect harmful surge energy to earth ground, 
resetting automatically waiting for the next surge. Operation 
is similar to a pressure relief valve on a water heater: pressure 
builds, valve opens to relieve pressure, resets when pressure 
drops. SPDs are capable of repeating this function thousands 
of times before needing replacement.

Voltage Rating & Application:

Before installing your STXP, verify by nameplate voltage or 
model number that it has the same voltage rating as the 
power distribution system. DO NOT INSTALL ANY LOWER 
VOLTAGE RATED PRODUCT. See attached Advisor Data 
Sheet or call Mersen Technical Services at (978) 465-4853 
for help.

The  system  configuration  is  defined  by  the  secondary 

windings of the transformer supplying the service entrance 
main or load. This includes whether or not the transformer 
windings are referenced to earth via a grounding conductor. 

The system configuration is not based on any specific load 

or equipment connection. SPDs should be installed per 
the distribution system, not per a load or motor’s wiring 
connection.  For example: A 480V three phase motor 
appears to be connected in 480V Delta. In reality, the 

distribution system is configured as a 480Y/277V grounded 

Wye, with or without a neutral pulled to the motor or MCC. 
The system is a 480Y/277V Wye, even though the load 

is  connected  as  a  Delta. A  grounded  Wye  has  a  defined 

reference to ground (i.e., neutral is bonded to ground). In 
contrast, some Delta systems are ungrounded, which have 
no reference to ground.

WARNING SPDs on Ungrounded Systems 
Caution

 – Ungrounded systems are inherently unstable 

and can produce excessively high line-to-ground voltages 
during certain fault conditions. During these fault conditions, 
any electrical equipment including SPDs, may be subjected 
to voltages which exceed their designed ratings. This 
information is being provided to the user so that an informed 
decision can be made before installing any electrical 
equipment on an ungrounded power system.

STXP Series SPDs have high SCCR (short circuit 
current ratings) capacity including the lead conductors. 
Supplemental overcurrent protection is not required to 
protect your STXR SPD. However, NEC

®

 convention 

requires that connecting conductors have overcurrent 
protection in Type 2 or 4 applications. Follow applicable 
codes. Your STXP device features internal overcurrent and 
over temperature protection that will disconnect effected 
surge suppression components at end of life. Power to the 
load is maintained but unprotected and the STXR should 
be replaced as soon as possible. The STXP SPD is factory 
sealed and contains no serviceable parts.

3.00

(76.20)

0.19

(4.83)

8.28

(210.31)

3.67

(93.22)

2.21

(56.13)

7.41

(188.21)

Weight: 3lbs (1.4kg)