background image

This would mean the plunger needs to be lowered.  To do this, the adjusting nut 

above and below the pivot connector need to be raised one turn.  This may need to be repeated again to completely stop the leak.  

Smaller adjustments are better than adjusting several turns at once, as it may not be necessary.  If three or so adjustments does not 

fix the leak, the plunger must be replaced.  Most likely it is damaged or worn excessively.  

Replace the Plunger

 

To replace the plunger, a piece of tape needs to be put around the standpipe just under the hydrant head and mark the location of 

the nozzle.  Turn off the water supply and unscrew the head from the standpipe and pull out the inside rod and plunger.  Replace 

the plunger, lubricate and install back in standpipe.  Tighten head so that the head touches the tape and likely no further 

adjustment will be necessary.  Test to make sure it is draining properly by holding your hand over the outlet nozzle right away 

after shutting off hydrant for a few seconds.  Remove hand and you should hear a sound of air rushing into the hydrant.  This 

means it is draining properly and should be in good working order.  If it is not, do the adjustment as described above. 

 

Leaking out of the Drain Hole

 

What you need to know is if it is leaking in the "off" position or the "on" position.  These are two completely different 

adjustments.  

"On" Position Leak

 

If it is leaking when in the "on" position, the plunger may be too low which means the plunger is not coming up far enough to 

shut off the drain hole when the hydrant is running.  Making small adjustments at a time is more critical in this situation.  Move 

the adjustment nuts down a half turn only.  By going too far you will raise the plunger so much it will not shut off when the 

handle is down, causing it to leak out of the nozzle.  If the leak does not stop, the plunger could be worn or damaged and needs to 

be replaced. 

"Off" Position Leak

 

If the leak continues when the hydrant is in the "off" position, the plunger needs a slight adjustment down.  This means that you 

need to raise the adjustment nuts up a half turn to make the plunger go down.  Again, if two or more adjustments does not fix the 

problem, the plunger needs to be replaced as in above directions.  

The only circumstances in which a hydrant would need to be dug up would be damage to the valve body or standpipe due to 

freezing weather or aggressive soil conditions and it rusted through.  No amount of adjusting will fix this and those parts would 

Содержание Any Flow Series

Страница 1: ...ick or stone would carry this weight Step 4 To connect the hydrant to the water line just turn it onto the male thread connection for which it is intended Merrill Manufacturing has hydrant ells and tee fittings available for connection to flexible poly pipe CAUTION When the hydrant is tightened be careful that it is not tightened so tightly that the hydrant head or valve body will be screwed furth...

Страница 2: ...nut upward only one thread then tighten the lower nut upward toward the G 25 pivot connector or raise the G 25 then tighten the top nut To determine if the water is not draining out of the stand pipe turn the hydrant on and let the water flow Then push down the handle to close the hydrant with a cup of water covering the nozzle If the water in the cup siphons back through the hydrant the plunger i...

Страница 3: ...oving the handle up and down Sometimes this may have to be repeated again and again depending on how long the leak has gone without being fixed Small adjustments are much better than turning the nut a full turn or more right away as that may not be necessary If the adjustments do not cure the leak a new packing piece must be installed under the packing nut There is no reason to shut off the water ...

Страница 4: ...order If it is not do the adjustment as described above Leaking out of the Drain Hole What you need to know is if it is leaking in the off position or the on position These are two completely different adjustments On Position Leak If it is leaking when in the on position the plunger may be too low which means the plunger is not coming up far enough to shut off the drain hole when the hydrant is ru...

Страница 5: ...d There is no reason to ever dig up a hydrant to fix a leak It is a 100 to 1 odds that a hydrant needs to be dug up to be fixed Consult with factory if system pressure is over 100 psi before installation of this product ...

Отзывы: