background image

Mercury Security Corporation, 

©

 2008

      BR20       Doc. 10107-0024  rev. 1.03  10/2008

  

                            

   Page 3

Information subject to change without notice.

9. BR20 Standard Format Code Summary:

The following formats are supported in standard models (31002-8000/31012-8000).

Unless otherwise indicated, the LED input line controls both LEDs (low=green, high=red); the BUZZER input
controls the buzzer (low = activate); a good read is signaled by a flash of the green LED; a bad read is signaled
by a flash of the red LED and a double beep of the buzzer.

Format  0  -

32-bit Wiegand compatible output from standard Northern Computer mag card. 16-bit facility code
and 16-bit user ID.  Reverse read and error filter is enabled.  Tamper monitor disabled.

Format 1 -

Basic mag-stripe data output: send track 2 data without any verification or formatting using 

CLOCK/

DATA

 signaling.  All reads are "good", card data sent as is.  Tamper monitor disabled.

Format 2 -

Mag-stripe data output with zero trim using 

CLOCK/DATA

 signaling.  All reads are "good", trims

excess zero bits, otherwise send data as is.  Tamper monitor enabled.

Format 3 -

Mag-stripe data output with zero trim, reverse read correction, and error filter enabled using 

CLOCK/

DATA

 signaling.  Tamper monitor disabled.

Format 4 -

26-bit Wiegand (8-bit fac. and 16-bit ID) compatible output from cards with 8 or more digits  or AMC
encoding.  See Format 5 for digit usage.  Tamper monitor disabled.

Format 5 -

34-bit Wiegand (12-bit fac. and 20-bit ID) compatible output from cards with 8 or more digits  or AMC
encoding.  Tamper monitor disabled.

 Facility Code

User ID

Digits in mag card

Digits

26-bit  Range

34-bit Range

Digits

26-bit Range

34-bit Range

8

1-3

000-255

000-999

4-8

00000-65535

00000-99999

9

1-3

000-255

000-999

4-9

000000-065535

000000-999999

10

1-4

0000-0255

0000-4097

5-10

000000-065535

000000-999999

11 or more

1-5

00000-00255

00000-04097

6-11

000000-065535

000000-999999

AMC card

1-6

000000-000255

000000-004097

7-12

000000-065535

000000-999999

Format 6 -

26-bit Wiegand compatible output from standard Northern Computer 32-bit mag-stripe card. The lower
8 bits of the 16-bit facility code is used as facility code.  The 16-bit user ID is unaltered. Reverse read
and error filter is enabled.  Tamper monitor disabled

Format 7 -

Mag-stripe data output with zero trim and reverse read correction using 

DATA 1/DATA 0

 signaling.

Tamper monitor disabled.

Format 12 -

Mag-stripe data output: send track 2 data without any verification or formatting using 

CLOCK/DATA

.

All reads are "good", card data is sent  as is.  2-wire LED control.  No buzzer control.  Tamper monitor
disabled.

Format 13 -

Mag-stripe data output with zero trim and reverse read correction using 

DATA 1/DATA 0

 signaling.

2-wire LED control.  No buzzer control.  Tamper monitor disabled.

Format 15 -

(factory test) mag-stripe data output: verify track 2 data and send track 2 data without formatting using

CLOCK/DATA

 signaling.  Zero trim, reverse read, bad card filter, and tamper monitor enabled.

10. Keypad Data Signaling:

Keypad data is transmitted on the data lines as 8-bit blocks. They are encoded and sent using the same signaling
method as selected for the card data output (clock/data or data 1/data 0).  If Dorado 8-bit keypad data format is required
order the -K1 option.  Card data, and keypad data blocks are separated by a minimum of 100 milliseconds. See following
for codes:

10110000  -  0 (ASCII '0', odd parity, MSB first)

00110001  -  1 (ASCII '1', ...)

00110010  -  2 (ASCII '2', ...)

10110011  -  3 (ACSII '3', ...)

00110100  -  4 (ASCII '4', ...)

10110101  -  5 (ASCII '5', ...)

10110110  -  6 (ASCII '6', ...)

00110111  -  7 (ASCII '7', ...)

00111000  -  8 (ASCII '8', ...)

10111001  -  9 (ASCII '9', ...)

00101010  -  * (ASCII '*', ...)

00100011  -  # (ASCII '#', ...)

11010011 - SAFE (ASCII 'S', ...)

01010100 - ALARM (ASCII 'T', ...)

Содержание BR20

Страница 1: ...ACH CA 90815 1755 562 986 9105 FAX 562 986 9205 CAUTION DONOTDISCONNECT KEYPADWITHOUTDISENGAGING THECONNECTOR 3 Reader Wiring ThereaderhasaRJ 11modularjackforeasyfieldconnection Ashortpieceofpre terminatedcableissuppliedwith eachstandardreaderforfieldwiring Thepre terminatedcablehasnonstandardcolor Refertopinnumberifthepre terminated cable is not used Cable with wires of 24AWG or larger are recomm...

Страница 2: ... the buzzer 2 wire control 0V turns on the green LED 6 Black SignalGround Power supply return DC ground 7 Grounding the Reader To avoid having ESD electrostatic discharge interfering with the operation of the reader the reader casing shall be grounded This can be accomplished by tying the mounting bracket to earth ground locally e g grounded conduit 8 DIP Switch Setting The DIP switch on the BR20 ...

Страница 3: ... 99999 9 1 3 000 255 000 999 4 9 000000 065535 000000 999999 10 1 4 0000 0255 0000 4097 5 10 000000 065535 000000 999999 11 or more 1 5 00000 00255 00000 04097 6 11 000000 065535 000000 999999 AMC card 1 6 000000 000255 000000 004097 7 12 000000 065535 000000 999999 Format 6 26 bitWiegandcompatibleoutputfromstandardNorthernComputer32 bitmag stripecard Thelower 8 bits of the 16 bit facility code is...

Страница 4: ...frequency lighttrafficorheavy traffic Extreme case may require daily cleaning Headcleaningmaybedonebyusingadisposable pre saturatedmagneticheadcleaningcard Thesecardsarereadily obtainable from a number of sources e g Clean Team Co www cleanteam com 800 888 8830 KIC Products www kicproducts com 207 514 7030 SystemID www systemid com 888 648 4452 The reader exterior surface is covered with high stre...

Страница 5: ...ication Readerproductidentificationisprovidedon labels TheselabelshaveinformationonprogramID revision productID supply voltage and copyright notice These labels are located on the circuit board and the back of the reader Optional Wall Plate part WP10 Fitting Rigid Conduit to Junction Box 15 Reader Mounting Dimensions 0 99 25 DIMENSION INCH mm MOUNTING HOLE 2X Ø 18 4 5 2 60 66 3 30 84 1 30 33 WALL ...

Страница 6: ...uthorize any agent or representative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for aparticularpurpose Returnedunitsarerepairedorreplacedfromastockofreconditionedunits Returnsmustbeaccompaniedbyareturnauthorizationnumber RMA obtainedfrom customer service and prepaid postage and insurance Liability The...

Отзывы: