 Grounded and foreign voltage states are not UL 294 required and therefore not verified by UL. 

The input circuit wiring configurations shown are supported, but may not be typical:  
 

 

M5-2K Input Wiring 

– Supervised and Non-supervised 

 

 

Door position monitor and REX inputs must be wired to the M5-2K when using F/2F readers.  EOL 
resistors are typically two 1K ohm resistors as shown below.  The EOL resistors should be installed 
as close to the switch as possible. 

 
M5-2K Input Terminal Block Definitions: 
 

TB1: Inputs 1 thru 5 

 

TB2: Inputs 6 thru 10 

TB1-1 

DI 1 

 

TB2-1 

DI 6 

TB1-2 

DI 1 return 

 

TB2-2 

DI 6 return 

TB1-3 

DI 2 

 

TB2-3 

DI 7 

TB1-4 

DI 2 return 

 

TB2-4 

DI 7 return 

TB1-5 

DI 3 

 

TB2-5 

DI 8 

TB1-6 

DI 3 return 

 

TB2-6 

DI 8 return 

TB1-7 

DI 4 

 

TB2-7 

DI 9 

TB1-8 

DI 4 return 

 

TB2-8 

DI 9 return 

TB1-9 

DI 5 

 

TB2-9 

DI 10 

TB1-10 

DI 5 return 

 

TB2-10 

DI 10 return 

 

 

10. Door Strike Wiring using an External Relay: 

Instead  of  using  the  on-board  relay  to  control  the  door  strike,  an  external  relay  may  be  used.    This 
external relay is controlled by the reader DOx output. 

If the LED in the reader is  driven by the reader port  DOx signal, a  blocking diode must be added to the 
circuit.  This blocking diode should be a Schottky barrier rectifier, type 1N5817 or equivalent (20 volt @ 1 
A). 
 
 

 

Important note: 

 

The external relay’s coil current must be  restricted to 40 mA.  The coil resistance of a 12 volt relay 
must be 300 ohms or greater. 
 

 

1K,1%

1K,1%

1K,1%

1K,1%

Standard Supervised Circuit,
Normally Open Contact

Normally Closed Contact

Standard Supervised Circuit,

Normally Closed Contact

Unsupervised Circuit,

Normally Open Contact

Unsupervised Circuit,

Содержание M5-2K

Страница 1: ...ormer The M5 2K supports the charging of an optional 12 Volt 7 Ah rechargeable sealed lead acid battery for UPS operation This installation manual does not contain the M5 IC controller board configura...

Страница 2: ...CR2330 TB2 RESET SWITCH DIP SWITCHES STATUS LEDS TB2 RS 485 TO DOWNSTREAM ENCLOSUES BATTERY BR CR2325 BR CR2330 REPLACE ANNUALLY J6 TO MICRO 5 BACKPLANE J7 J7 CONNECTION TO OPTIONAL MICRO125 STANDOFF...

Страница 3: ...Volt Battery positive terminal TB8 8 12 Volt Battery negative terminal Do not use a 24 Vac transformer to power the M5 2K M5 IC assembly There must be no wires connected to TB1 of the M5 IC 4 Ethernet...

Страница 4: ...ON OFF OFF ON OFF Address 10 OFF ON OFF ON OFF Address 11 ON ON OFF ON OFF Address 12 OFF OFF ON ON OFF Address 13 ON OFF ON ON OFF Address 14 OFF ON ON ON OFF Address 15 ON ON ON ON OFF Address 16 OF...

Страница 5: ...figurations 1 Supervised F 2F readers door contacts and REX inputs are to be wired through the reader 2 F 2F readers door contacts and REX inputs must be wired to the M5 2K inputs see Section 9 Typica...

Страница 6: ...only the open or closed states When an input circuit is configured for supervision the M5 2K board also monitors the following abnormal circuit conditions open circuit shorted circuit grounding of eit...

Страница 7: ...DI 8 TB1 6 DI 3 return TB2 6 DI 8 return TB1 7 DI 4 TB2 7 DI 9 TB1 8 DI 4 return TB2 8 DI 9 return TB1 9 DI 5 TB2 9 DI 10 TB1 10 DI 5 return TB2 10 DI 10 return 10 Door Strike Wiring using an Externa...

Страница 8: ...n of other equipment To minimize premature contact failure and to increase system reliability a contact protection circuit must be used Locate the protection circuit as close to the load as possible 1...

Страница 9: ...00 ms ON 800 ms OFF On line Non encrypted communication flash cycle of 800 ms ON 200 ms OFF Encrypted communication 4 flash cycles in 700 ms ON then 300 ms OFF Error Indication Waiting for firmware do...

Страница 10: ...s maximum loop resistance Outputs As required for the load Reader data Use shielded cables 12 Vdc 20 AWG 500 feet maximum reader powered by M5 2K board 18 AWG 3000 feet maximum reader powered locally...

Страница 11: ...esentative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompa...

Отзывы: