Mercury Security M5-2K Скачать руководство пользователя страница 5

 

Mercury Security © 2014 

M5-2K 

DOC  10107-0048 

REV 1.02 

Page   5 

 

7.  Reader Wiring: 

Each of the four reader ports support F/2F, and supervised F/2F type readers. 

Reader cable requirements:

  See specification section for more details. 

  F/2F and supervised F/2F readers require a shielded 4-conductor cable. 

 

 

F/2F or Supervised F/2F Reader 

 

M5-2K Reader Port Terminal Block Definitions: 

 

TB3: Reader Port 1 

 

TB4: Reader Port 2 

 

TB5: Reader Port 3 

 

TB6: Reader Port 4 

TB3-1 

+12 Vdc 

 

TB4-1 

+12 Vdc 

 

TB5-1 

+12 Vdc 

 

TB6-1 

+12 Vdc 

TB3-2 

GND 

 

TB4-2 

GND 

 

TB5-2 

GND 

 

TB6-2 

GND 

TB3-3 

DI 

 

TB4-3 

DI 

 

TB5-3 

DI 

 

TB6-3 

DI 

TB3-4 

DO1 

 

TB4-4 

DO2 

 

TB5-4 

DO3 

 

TB6-4 

DO4 

 

8.  Door Position Monitor and REX Input Wiring: 

The door position monitor and REX switches can be wired in two different configurations.   

1.  Supervised F/2F readers: door contacts and REX inputs are to be wired through the reader 
2.  F/2F readers: door contacts and REX inputs must be wired to the M5-2K inputs, see Section 9 

Typically, the door position monitor switch uses the Normally  Close (NC) contact and the REX uses the 
Normally  Open  (NO)  contact.    Some  supervised  F/2F  readers  support  different  switch  configurations 
which are defined in the host and downloaded to the M5-2K. 

Supervised Inputs - Wired to Supervised F/2F Reader, 4-State Supervision: 

Supervised  inputs  for  the  door  position  monitor  and  REX  switches  are  wired  directly  to  the  supervised 
F/2F  reader  configured  for  4-State  Supervision

.   See reader’s documentation for the  proper  connection 

terminals.    Typically,  the  EOL  resistors  are  two  1K  ohm  resistors  as  shown  below.    The  EOL  resistors 
should be installed as close to the switch as possible. 

DI

DOx

3

DI

4

LED

+12 Vdc

GROUND

1

VO

2

GND

1

F/2F Reader

4

Содержание M5-2K

Страница 1: ...ormer The M5 2K supports the charging of an optional 12 Volt 7 Ah rechargeable sealed lead acid battery for UPS operation This installation manual does not contain the M5 IC controller board configura...

Страница 2: ...CR2330 TB2 RESET SWITCH DIP SWITCHES STATUS LEDS TB2 RS 485 TO DOWNSTREAM ENCLOSUES BATTERY BR CR2325 BR CR2330 REPLACE ANNUALLY J6 TO MICRO 5 BACKPLANE J7 J7 CONNECTION TO OPTIONAL MICRO125 STANDOFF...

Страница 3: ...Volt Battery positive terminal TB8 8 12 Volt Battery negative terminal Do not use a 24 Vac transformer to power the M5 2K M5 IC assembly There must be no wires connected to TB1 of the M5 IC 4 Ethernet...

Страница 4: ...ON OFF OFF ON OFF Address 10 OFF ON OFF ON OFF Address 11 ON ON OFF ON OFF Address 12 OFF OFF ON ON OFF Address 13 ON OFF ON ON OFF Address 14 OFF ON ON ON OFF Address 15 ON ON ON ON OFF Address 16 OF...

Страница 5: ...figurations 1 Supervised F 2F readers door contacts and REX inputs are to be wired through the reader 2 F 2F readers door contacts and REX inputs must be wired to the M5 2K inputs see Section 9 Typica...

Страница 6: ...only the open or closed states When an input circuit is configured for supervision the M5 2K board also monitors the following abnormal circuit conditions open circuit shorted circuit grounding of eit...

Страница 7: ...DI 8 TB1 6 DI 3 return TB2 6 DI 8 return TB1 7 DI 4 TB2 7 DI 9 TB1 8 DI 4 return TB2 8 DI 9 return TB1 9 DI 5 TB2 9 DI 10 TB1 10 DI 5 return TB2 10 DI 10 return 10 Door Strike Wiring using an Externa...

Страница 8: ...n of other equipment To minimize premature contact failure and to increase system reliability a contact protection circuit must be used Locate the protection circuit as close to the load as possible 1...

Страница 9: ...00 ms ON 800 ms OFF On line Non encrypted communication flash cycle of 800 ms ON 200 ms OFF Encrypted communication 4 flash cycles in 700 ms ON then 300 ms OFF Error Indication Waiting for firmware do...

Страница 10: ...s maximum loop resistance Outputs As required for the load Reader data Use shielded cables 12 Vdc 20 AWG 500 feet maximum reader powered by M5 2K board 18 AWG 3000 feet maximum reader powered locally...

Страница 11: ...esentative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompa...