9.  Relay Circuit Wiring: 

Two Form-C contact relays are provided for controlling door lock mechanisms or alarm signaling devices.  
The relay contacts are rated at 2 A @ 30 Vdc, dry contact configuration.  Each relay has a Common pole 
(C), a Normally Open pole (NO) and a Normally Closed pole (NC).  When you are controlling the delivery 
of  power  to  the  door  strike,  the  Normally  Open  and  Common  poles  are  used.    When  momentarily 
removing  power  to  unlock  the  door,  as  with  a  mag  lock,  the  Normally  Closed  and  Common  poles  are 
used.  Check with local building codes for proper egress door installation. 

Door  lock  mechanisms  can  generate  EMF  feedback  to  the  relay  circuit  that  can  cause  damage  and 
premature  failure  of  the  relay.    For  this  reason,  it  is  recommended  that  either  a  diode  or  MOV  (metal 
oxide varistor) be used to protect the relay.  Wire should be of sufficient gauge to avoid voltage loss. 

 

From the Auxiliary output, the EP1501 can provide 12 Vdc power for external devices provided that the 
maximum current is not exceeded.  See the specifications section for details.  If a local power supply is 
used, it must be UL Listed Class 2 rated. 
 

Relay Circuit Wiring Diagrams: 

 

 

10.  Memory Backup Battery: 

The SRAM is backed up by a rechargeable battery when input power is removed.  This battery should 
retain the data for a minimum of 3 days.  If data in the SRAM is determined to be corrupt after power up, 
all data, including flash memory, is considered invalid and is erased.  All configuration data must be re-
downloaded. 

 

Note:  

The initial charge of the battery may take up to 48 hours to be fully charged. 

 
 
 
 
 
 

 

Diode Selection: 
 

Diode current rating: 1x strike current 
Diode breakdown voltage: 4x strike voltage 
For 12 Vdc or 24 Vdc strike, diode 1N4002 
(100V/1A) typical. 

 

 

MOV Selection: 
 

Clamp voltage: 1.5x Vac RMS. 
Use UL recognized MOV with appropriate 
ratings 

 

TB5

1

NO
1-C
NC

NC

NO

2-C

Содержание EP1501

Страница 1: ...ol and buzzer control one wire LED mode only This port can also utilize multiple 2 wire RS 485 multi dropped devices such as up to two readers or up to eight remote serial I O devices Reader port 2 can accommodate a reader that utilizes TTL D1 D0 Clock Data or F 2F signaling also provides tri state LED control and buzzer control one wire LED mode only Two Form C contact relay outputs may be used f...

Страница 2: ... Vdc TB4 2 GND Auxiliary Power Output Ground TB4 3 VIN Input Power 12 Vdc from local power supply TB4 4 GND Input Power Ground TB5 1 NO Relay K1 Normally Open Contact TB5 2 1 C Relay K1 Common Contact TB5 3 NC Relay K1 Normally Closed Contact TB5 4 NO Relay K2 Normally Open Contact TB5 5 2 C Relay K2 Common Contact TB5 6 NC Relay K2 Normally Closed Contact Jumpers JUMPERS SET AT DESCRIPTION J1 N A...

Страница 3: ...d for the following purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing EP1501 board to continuously reboot If clearing the memory does not correct the initialization problem contact technical support Bulk Erase Steps Do not remove power during steps 1 8 1 Set S1 DIP switches ...

Страница 4: ...vices If two OSDP devices are used reader port 2 will not support a third reader If only one OSDP device is configured then reader port 2 is available for a second reader The maximum cable length is 2000 ft 610 m Do not terminate any RS 485 devices connected to reader port 1 When powering remote device s from the EP1501 be cautious not to exceed the maximum current limit Cable gauge must also be e...

Страница 5: ...ROUND DO GREEN LED F 2F Reader 1K 1 1K 1 1K 1 1K 1 SECOND READER PORT TB3 TB4 DOOR MONITOR SWITCH NORMALLY CLOSED CONTACT REQUEST TO EXIT SWITCH NORMALLY OPEN CONTACT FIRST READER PORT 1 BZR VO DAT D0 CLK D1 LED GND VIN GND TB4 TB3 1 VO 12 Vdc CLK LED BZR GND DAT TB2 1 REMOTE SERIAL I O MODULE REMOTE SERIAL I O MODULE MR16in MR16out FOR EXAMPLE MRDT MR50 MR52 GND GND 12 Vdc TR TR MRDT FOR EXAMPLE ...

Страница 6: ...re Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL The input circuit wiring configurations shown are supported but may not be typical VO 12 Vdc GND DAT CLK 1 OSDP PROTOCOL DEVICE 9600 BAUD ADDRESS 0 BZR 1 GND GND VIN VO DAT D0 CLK D1 1 LED LED BZR OSDP PROTOCOL DEVICE ADDRESS 1 9600 BAUD REFER TO THE APPROPRIATE REMOTE SERIAL I O DEVICE INSTALLA...

Страница 7: ...e varistor be used to protect the relay Wire should be of sufficient gauge to avoid voltage loss From the Auxiliary output the EP1501 can provide 12 Vdc power for external devices provided that the maximum current is not exceeded See the specifications section for details If a local power supply is used it must be UL Listed Class 2 rated Relay Circuit Wiring Diagrams 10 Memory Backup Battery The S...

Страница 8: ...de Flashes when Data Acknowledgment is Received 4 Input IN1 Status OFF Inactive ON Active Flash Trouble See Note 1 5 Input IN2 Status OFF Inactive ON Active Flash Trouble See Note 1 6 Cabinet Tamper 7 Reserved for Future Use YEL Ethernet Speed OFF 10 Mb S ON 100 Mb S GRN OFF No Link ON Good Link Flashing Ethernet Activity Note 1 If this input is defined every three seconds the LED is pulsed to its...

Страница 9: ...sistive Reader Interface Power 12 Vdc 10 PoE or local power supply 180 mA maximum Data Inputs Reader port 1 TTL compatible F 2F or 2 wire RS 485 Reader port 2 TTL compatible or F 2F LED Output TTL compatible high 3 V low 0 5 V 5 mA source sink maximum Buzzer Output Open collector 12 Vdc open circuit maximum 40 mA sink maximum Cable Requirements Power 1 twisted pair 18 AWG when using local 12 Vdc p...

Страница 10: ...art number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 Mounting Plate Dimensions FIELD WIRING EP1501 WITH INCLUDED MOUNTING PLATE TO ETHERNET NETWORK OPTIONAL 3 GANG JUNCTION BOX OPTIONAL BLANK COVER W SCREWS OPTIONAL MAGNETIC TAMPER SWITCH 3 85 97 8 2 35 59 7 5 50 139 7 3 63 92 1 3 30 83 8 3 63 92 1 Ø0 16 Ø4 0 MR50 MGT HOLES 4PL Ø0 16 Ø4 0 3 GANG MGT HOLES 4PL ...

Страница 11: ...resentative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an al...

Отзывы: