Earth Leakage Relay 

ME-ELR-DD

Indicator

Status

Trip

Alarm

FUNC

DP

DATA

0

0

0

0

0

No auxiliary power supply

0

0

0

0

1

Normal condition, no tripping

0

B

X

X

X

Leakage current exceeded 50% of the sensitivity

setting, I

n

0

FB

X

X

X

Leakage current exceeded 85% of the sensitivity

setting, I

n. Time delay countdown started

1

1

0

0

B

Delay time lapsed and relay tripped

0

X

1

0

1

Scroll through setting

0

X

1

1

1

Scroll through records

0

X

B

0

1

Programming mode

Light Indicators

The indicators display the status of the system as follow:

Indicators

Pre-fault alarm

Red indicator

Time delay

Red indicator

Leakage trip

7-segment display &

red indicator

ME-T fault

7-segment display & red indicator

Real-time leakage current

7-segment display

Zero-Phase Current Transformer

To operate with Mikro's ME-T series of current transformer

Delay time adjustment

0.05s - 0.5s (Step = 0.05s)

Mechanical

Mounting method

Standard 35mm DIN rail mounting

Approximate weight

0.38kg (excluding ME-T)

a - Trip status indicator
b -  Model
c - Alarm status indicator
d - Up button
e - Down button
f - Reset/mode button

g - Integral test button
h - DP indicator
i - FUNCTION indicator
j - DATA indicator

Symbols
I

n - Sensitivity setting

t - Time delay setting

Flt 1 - Fault record 1 (Newest)
Flt 2 - Fault record 2
Flt 3 - Fault record 3 (Oldest)

Содержание ME-ELR-DD

Страница 1: ... comes with a pre fault alarm contact and a positive safety contact The pre fault alarm contact is energized when ever the leakage current exceed 50 of the sensitivity setting I n The positive safety contact is energized if the relay is power up and function correctly Description Applications Technical Data Industrial equipment protection Personnel protection from Earth Leakage faults Suitable for...

Страница 2: ...cators display the status of the system as follow Indicators Pre fault alarm Red indicator Time delay Red indicator Leakage trip 7 segment display red indicator ME T fault 7 segment display red indicator Real time leakage current 7 segment display Zero Phase Current Transformer To operate with Mikro s ME T series of current transformer Delay time adjustment 0 05s 0 5s Step 0 05s Mechanical Mountin...

Страница 3: ...Integral Trip Test Press the TEST button to perform an integral test on the relay ranging from analog sensing circuitry to output contact s of the relay as well as the relay indicators and display b Trip Reset Press the RESET button to reset the relay when tripped c CT Fault Press the RESET button to reset the relay after fixing the ME T connection error No reset function is carry out if the fault...

Страница 4: ...r fixing the ME T connec tion error To reset the relay make a connection between terminals 4 and 5 of the relay Output Contact a Trip Contact This is the latching type contact It is energized either relay tripped due to leakage fault or broken connection between the relay and the ME T b Positive Safety Contact Contact energized when the relay is power up and function correctly with no tripping c P...

Отзывы: