mcr S-THERM smoke exhaust vents: C, E, NG-A. OPERATION AND MAINTENANCE MANUAL
Page 14 of 41
1. Diagonal steel base of vent
2. Thermal insulation of the base
3. Membrane or roofing paper
4. Roof thermal insulation
5. Trapezoidal sheet
6. Load-bearing steel structure
Fig. 19 Diagonal steel base on steel structure.
5.4.
Mounting of soft body impact safety nets for an impact energy of 1200 J
Safety nets with impact energy up to 1200 J are optional. However, when only the base of the vent is
installed on the roof (e.g. in connection with dividing the works into stages), it is obligatory to take care
of safety considerations and protect its entire clear opening with a set of nets mounted on the base
through appropriate consoles.
NOTE: never leave bases with unprotected clear opening on the roof!
The correct protection of the full length of the base consists of:
1. Standard nets - fixed
(protect the space between the opening system and the sides of the base)
2. Temporary net - removable
(protects the centreportion of the clear opening until the frame and opening system are installed).
Fig. 20 Folding base protected by nets along its entire length.
1
2