MERCOR SA – 

The Company reserves the right to make modifications and changes.

 

6/9 

5. DESIGNATION OF THE DAMPER  __________________________________  

 

mcr PL1     B x H   /   Z         

 
 
 
 
 
 
 
 
 
 

 

6. INSTALLATION OF THE DEVICE  __________________________________  

The  mcr  PL1  damper  is  designed  for  vertical  installation.  Due  to  the  special  operation  of  the  device 
and the applied technical solutions, the damper has to be mounted in a suitable position according to the 
instructions given on the casing by the manufacturer. 
 
 

6.1.  PRE-INSTALLATION INSPECTION __________________________________________  

Each  damper  is  inspected  before  packing  and  shipment  by  the  manufacturer.  After  unpacking  at  the 
recipient,  perform  visual  inspection  to  check  if  the  casing  has  not  been  deformed  and  whether  the 
damper has not been damaged during transport. 
 
 

6.2.  INSTALLATION OPENING _________________________________________________  

The minimum size of the opening permitting correct installation of the damper is (B+30)x(H+30)mm. 

 

 

 

 

 

              góra

 Kierunkek przepływu

              dół 

 

Installation opening 

Direction and position of a damper installation 

 

 
 
 
 
version (K – duct-mounted, S – wall-mounted) 
 
gross dimensions of the damper: breadth x height 
[mm]  
commercial designation – a damper without 
accessories 

Flow direction 

top 

bottom 

Содержание mcr PL1

Страница 1: ... 08 GDAŃSK 2008 ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 0 58 341 39 85 TECHNICAL AND OPERATIONAL DOCUMENTATION Overpressure bleed damper of mcr PL1 type FIRE VENTILATION SYSTEMS DEPARTMENT ...

Страница 2: ... THE DOCUMENTATION 3 3 PURPOSE OF THE DEVICE 3 4 CONSTRUCTION AND PRINCIPLE OF OPERATION OF THE DEVICE 3 5 DESIGNATION OF THE DEVICE 6 6 INSTALLATION OF THE DEVICE 6 6 1 PRE INSTALLATION INSPECTION 6 6 2 INSTALLATION OPENING 6 6 3 EMBEDDING 7 6 4 ELECTRICAL CONNECTIONS 8 7 TRANSPORT AND STORAGE CONDITIONS 8 8 MAINTENANCE AND SERVICE 8 9 TERMS OF GUARANTEE 9 ...

Страница 3: ...r partition thus operating as so called safety valves that prevent the increase of pressure above a set value e g in a protected staircase The devices meet the requirements of the PN EN 12101 6 standard Fire Resistance ___________________________________________________________________ The device does not feature fire resistance as it is not required for its correct operation Execution Versions __...

Страница 4: ...uitable flow of an air stream Driving and Tripping Systems ____________________________________________________ The driving system of mcr PL1 dampers is made of suitably selected steel weights that are mounted on blades of the device Dimensions _______________________________________________________________________ Mcr PL1 dampers are manufactured in the following dimensions Height Breadth B mm H ...

Страница 5: ...ssembly sets are made of a suitable number of single dampers of the basic type as well as flat bars and connecting elements Basic dimensions of mcr PL1 dampers have been presented on the drawing below 3 2 4 1 Technical characteristics 50 55 60 65 70 75 80 85 90 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 discharge V m3 h pressure P Pa PL500x500 PL600x600 PL750x750 PL400x400 NOTE Net dime...

Страница 6: ...TION INSPECTION __________________________________________ Each damper is inspected before packing and shipment by the manufacturer After unpacking at the recipient perform visual inspection to check if the casing has not been deformed and whether the damper has not been damaged during transport 6 2 INSTALLATION OPENING _________________________________________________ The minimum size of the open...

Страница 7: ...mper with protective film or other covering material before installation until the masonry and finishing work is completed After the concrete mortar sets remove the brackets and open individual blades of the damper manually to check if they operate correctly Connection of the embedded damper to the ventilation duct must be executed coaxially During installation of the damper in the partition a dam...

Страница 8: ...r each transport each damper should be visually inspected The damper must not be hit or dropped During handling and installation attention should be paid to the damper baffle The dampers should be stacked in no more than 2 layers vertically in closed rooms ensuring protection against external weather conditions In the case of storing of the dampers on the ground they should be placed on protective...

Страница 9: ...ull value with no financial consequences to the purchaser 5 The guarantee does not include the operations performed by the purchaser user specified in the Documentation 6 The Manufacturer is absolved from the guarantee and any obligations resulting from the guarantee if a the product has mechanical damage created due to improper transport or unloading using own means of the purchaser improper inst...

Отзывы: