1. INTRODUCTION
The aim of this Operation and Maintenance Manual is to make the user familiar with the intended use, design,
operating principle, correct installation and operation of the product. The OMM also contains additional information
on the conditions of use, maintenance and warranty of the product.
2. SUBJECT OF THE MANUAL
This OMM applies to a whole group of mcr FID PRO type single-plane fire dampers. Complying with the
recommendations included in the OMM will ensure proper functioning of the fire damper in its purpose of being a fire
protection system used in interior spaces as well as the safety of its users.
3. INTENDED USE OF THE FIRE DAMPER
Use
The mcr FID PRO type single-plane fire dampers may be used as:
mcr FID PRO/S fire dampers
mcr FID PRO/V fire dampers for fire ventilation systems
mcr FID PRO/M fire dampers for mixed-mode fire ventilation systems
mcr FID PRO/T transfer dampers
mcr
FID PRO/G pressure relief dampers
Fire dampers are not designed to work in ventilation systems where there is a risk of them coming into contact with
dust-laden air unless they have been covered by a special, tailor-made service and technical inspections programme.
Fire resistance
The fire resistance ratings of the mcr FID PRO type fire dampers are as follows:
EI60S
/S /V /M /T /G
EI120S
/S /V /M /T /G
EI60
/S /V /M /T /G
EI120
/S /V /M /T /G
E60S
/S /V /M /T /G
E120S
/S /V /M /T /G
E60
/S /V /M /T /G
E120
/S /V /M /T /G
The fire ratings depend on the use as well as the manner and place of fire damper installation.
Manufacturing versions
The mcr FID PRO type fire dampers may be manufactured as:
rectangular fire dampers
rectangular fire dampers with circular connections
round fire dampers
Size range
The mcr FID PRO type fire dampers are manufactured in the following dimensions:
width: from 100 to 315 mm
width for nipple fire dampers: 170 mm (with an option to be extended to 310 mm)
width for coupling fire dampers: 140 mm (with an option to be extended to 280 mm)
The fire dampers may be additionally fitted with connection flanges.
Apart from the standard dimensions, there is a possibility to manufacture fire dampers with any dimensions within
the above ranges. The maximum surface area of the mcr FID PRO type fire damper is 0.078 m
2
. The minimum
surface area of these fire dampers is 0.008 m
2
.
4. DESIGN AND OPERATING PRINCIPLE OF THE FIRE DAMPER
Design
The mcr FID PRO single-plane fire dampers consist of a housing with a round cross section, movable cut-off partition
as well as a release and control mechanism which is started remotely or automatically (after a thermal release has
been actuated). Fire dampers’ housings are made of galvanised steel sheet or stainless steel sheet. In the fire
damper’ housing, along its perimeter, there is an insulation perforation of suitable width. The fire damper’s cut-off
partition is made of non-flammable board. The partition is lined on both sides with sheet metal reinforcement. On the