mcr FID PRO
single-plane fire dampers
„MERCOR” SA –
the Company reserves the right to make modifications and changes.
11/24
1. Fire damper
2. E.g. cement mortar
3. Wall
4. Ventilation duct
X – wall thickness
The minimum depth of filling with mortar for the length of the body of the device.
Installation of the mcr FID PRO fire damper with a spring mechanism
in masonry walls, brickwork walls or blockwork walls
using mortar
1. Fire damper
2. Mineral wool with a density min. 150 kg/m3
3. mcr Polylack Elastic 1mm thick
4. Wall
5. Ventilation duct
X – wall thickness
The minimum depth of filling with mortar for the length of the body of the device.
Installation of the mcr FID PRO fire damper with a spring mechanism
in masonry walls, brickwork walls or blockwork walls using mineral wool