PrSt
Pump Run Time Reset: Select
0n
or
0FF
. Selecting
0n
will allow Pump Run
Time to be reset in the Secondary menu while an
0FF
selection will not allow
Pump Run Time to be reset.
SPH
Set Point High: Select from the highest input range value to
SPL
value. This will set
the maximum
SP1H
or
SP2H
value that can be entered. The value for
SP1H
or
SP2H
will stop moving when this value is reached. Factory Default is
23.1
.
SPL
Set Point Low: Select from the lowest input range value to
SPH
value. This will set
the minimum
SP1L
or
SP2L
value that can be entered. The value for
SP1L
or
SP2L
will stop moving when this value is reached. Factory Default is
0.0
.
S1Pi
Setpoint 1 Power Interrupt. Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Power Interrupt is
0n
. Output will automatically reset on
power-up if no alarm condition exists.
0FF
Alarm Power Interrupt is
0FF
. Output will be in the alarm condition
on power-up regardless of condition of process.
S1iH
Setpoint 1 Inhibit: Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Inhibit is
0n
. Alarm action is suspended until the process
value first enters a non-alarm condition.
0FF
Alarm Inhibit is
0FF
.
S2Pi
Setpoint 2 Power Interrupt. Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Power Interrupt is
0n
. Output will automatically reset on
power-up if no alarm condition exists.
0FF
Alarm Power Interrupt is
0FF
. Output will be in the alarm condition
on power-up regardless of condition of process.
S2iH
Setpoint 2 Inhibit: Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Inhibit is
0n
. Alarm action is suspended until the process
value first enters a non-alarm condition.
0FF
Alarm Inhibit is
0FF
.
S2ti
Setpoint 2 Time Delay. Select from 0 to 60 seconds. Factory default is 0. This will
set a time delay for setpoint 2 on power up of the MPC that will assure that
setpoint 2 will not be brought into use until after the programmed time delay.
PEA
The Peak feature stores the highest input the control has measured since the last
reset or Power On. At Power On
PEA
is reset to the present input. To manually
reset the value
PEA
must be in the lower display. Press the ENTER key to
reset.
PEA
will be reset and display the present input value.
UAL
The Valley feature stores the lowest input the Controller has measured since the
last reset or Power On. At Power On
UAL
is reset to the present input. To
manually reset the value
UAL
must be in the lower display. Press the
ENTER key.
UAL
will be reset and display the present input value.
19
ALAR
Cauti
enda
When
differe
Since
progr
one in
point
were
When
alarm
requir
will co
When
progr
subse
If Ala
the p
as if a
secon
The f
AL1
L-20:L-20 9/30/10 11:09 AM Page 19